What Wire Size for 125 Amps?

Copper Wire
1 AWG
7.3481 mm · 42.4077 mm²
Aluminum Wire
2/0 AWG
9.2658 mm · 67.4309 mm²
Breaker: 125A · Based on NEC Table 310.16, 75°C column (NEC 110.14(C) above 100A)

125-Amp Wire Size by Termination Rating

RuleCopperAluminum
75°C column — NEC Table 310.161 AWG2/0 AWG
Dwelling service or main feeder — NEC 310.12 (83% = 103.75A)2 AWG1/0 AWG

Above 100A, NEC 110.14(C)(1)(b) allows the 75°C column when terminations are rated 75°C, which is standard for this equipment.

Common Uses for 125A Circuits

Service entrance, large main panels

1 AWG Copper — Key Specs

Diameter7.3481 mm (0.289297")
Area42.4077 mm²
Resistance at 20°C0.4065 Ω/km
Weight379.973 kg/km
Ampacity (75°C)130 A

Important: For long wire runs, you may need to upsize the wire to compensate for voltage drop. NEC recommends keeping voltage drop under 3% for branch circuits. Use our voltage drop calculator to check.

Voltage Drop by Distance — 1 AWG Copper at 125A

One-way run Drop % of 240V Verdict
25 ft0.96 V0.4%Within the 3% branch-circuit target
50 ft1.93 V0.8%Within the 3% branch-circuit target
75 ft2.89 V1.2%Within the 3% branch-circuit target
100 ft3.85 V1.6%Within the 3% branch-circuit target
150 ft5.78 V2.4%Within the 3% branch-circuit target
200 ft7.70 V3.2%Over 3% — upsize one gauge
Single-phase, 240V, full 125A load, 0.154 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. Voltage drop is a performance recommendation, not a code requirement — but exceeding it causes dim lights, slow motor starts, and wasted energy.

Aluminum Feeder Specifications

Aluminum has about 61% of copper’s conductivity, so a 125A feeder that takes 1/0 AWG copper needs 2/0 AWG aluminum — typically one to two gauge sizes larger.

Aluminum conductor2/0 AWG
Ampacity (75°C, Table 310.16)135 A
Copper equivalent1 AWG (130 A)
Resistance0.1198 Ω/1000 ft
Voltage drop at 100 ft, 125A3.98 V (1.7% of 240V)

Installing aluminum correctly

  • Modern aluminum building wire must be AA-8000 series alloy (NEC 310.14(A)(1)). The 1960s-era AA-1350 alloy behind aluminum’s bad reputation is no longer permitted for branch circuits.
  • Terminate only on lugs and breakers marked AL/CU or AL9CU. Copper-only terminals are the most common failure point.
  • Apply an antioxidant compound to the stripped conductor before landing it, unless the termination is listed as not requiring it.
  • Torque every connection to the manufacturer’s value with a calibrated torque tool — NEC 110.14(D) makes this mandatory. Loose aluminum terminations are the primary cause of feeder failures.
  • Aluminum runs roughly half the weight and a third to half the cost of copper at feeder sizes, which is why it dominates service entrance and sub-panel feeders.

Frequently Asked Questions

What wire size do I need for 125 amps?

For a 125-amp circuit, NEC Table 310.16 at 75°C calls for 1 AWG copper (130A) or 2/0 AWG aluminum (135A). If it is the service or main feeder for a dwelling, NEC 310.12 allows sizing at 83% (103.75A): 2 AWG copper or 1/0 AWG aluminum.

What breaker do I need for 125 amps?

A 125-amp circuit uses a 125A double-pole circuit breaker. The breaker protects the 1 AWG copper (or 2/0 AWG aluminum) wire from overload. Double-pole breakers are used for 240V circuits and occupy two slots in the panel.

What is 1 AWG wire used for?

1 AWG copper is rated 130A at 75°C per NEC Table 310.16 (110A at 60°C), which makes it the minimum copper size for a 125A circuit above 100A. It is used for 125A feeders, large sub-panels and, under NEC 310.12, 150A dwelling services. 1 AWG aluminum is rated 100A.

What is the difference between 100A and 125A panels?

A 125A main breaker provides 25% more capacity than a 100A breaker. The conductors step up too: a 125A circuit needs 1 AWG copper or 2/0 aluminum under Table 310.16, while a 100A feeder needs 1 AWG copper or 1/0 aluminum at 60°C. The extra capacity gives headroom for an EV charger or additional appliances.

Wire size for other amperages

Related

Circuit breaker size chart → Wire types and insulation ratings → NEC Table 250.122 — ground wire size → 1 AWG full specifications → Full AWG chart → Wire size calculator → Ampacity tables →