| Rule | Copper | Aluminum |
|---|---|---|
| 75°C column — NEC Table 310.16 | 1 AWG | 2/0 AWG |
| Dwelling service or main feeder — NEC 310.12 (83% = 103.75A) | 2 AWG | 1/0 AWG |
Above 100A, NEC 110.14(C)(1)(b) allows the 75°C column when terminations are rated 75°C, which is standard for this equipment.
Service entrance, large main panels
| Diameter | 7.3481 mm (0.289297") |
| Area | 42.4077 mm² |
| Resistance at 20°C | 0.4065 Ω/km |
| Weight | 379.973 kg/km |
| Ampacity (75°C) | 130 A |
Important: For long wire runs, you may need to upsize the wire to compensate for voltage drop. NEC recommends keeping voltage drop under 3% for branch circuits. Use our voltage drop calculator to check.
| One-way run | Drop | % of 240V | Verdict |
|---|---|---|---|
| 25 ft | 0.96 V | 0.4% | Within the 3% branch-circuit target |
| 50 ft | 1.93 V | 0.8% | Within the 3% branch-circuit target |
| 75 ft | 2.89 V | 1.2% | Within the 3% branch-circuit target |
| 100 ft | 3.85 V | 1.6% | Within the 3% branch-circuit target |
| 150 ft | 5.78 V | 2.4% | Within the 3% branch-circuit target |
| 200 ft | 7.70 V | 3.2% | Over 3% — upsize one gauge |
Aluminum has about 61% of copper’s conductivity, so a 125A feeder that takes 1/0 AWG copper needs 2/0 AWG aluminum — typically one to two gauge sizes larger.
| Aluminum conductor | 2/0 AWG |
| Ampacity (75°C, Table 310.16) | 135 A |
| Copper equivalent | 1 AWG (130 A) |
| Resistance | 0.1198 Ω/1000 ft |
| Voltage drop at 100 ft, 125A | 3.98 V (1.7% of 240V) |
For a 125-amp circuit, NEC Table 310.16 at 75°C calls for 1 AWG copper (130A) or 2/0 AWG aluminum (135A). If it is the service or main feeder for a dwelling, NEC 310.12 allows sizing at 83% (103.75A): 2 AWG copper or 1/0 AWG aluminum.
A 125-amp circuit uses a 125A double-pole circuit breaker. The breaker protects the 1 AWG copper (or 2/0 AWG aluminum) wire from overload. Double-pole breakers are used for 240V circuits and occupy two slots in the panel.
1 AWG copper is rated 130A at 75°C per NEC Table 310.16 (110A at 60°C), which makes it the minimum copper size for a 125A circuit above 100A. It is used for 125A feeders, large sub-panels and, under NEC 310.12, 150A dwelling services. 1 AWG aluminum is rated 100A.
A 125A main breaker provides 25% more capacity than a 100A breaker. The conductors step up too: a 125A circuit needs 1 AWG copper or 2/0 aluminum under Table 310.16, while a 100A feeder needs 1 AWG copper or 1/0 aluminum at 60°C. The extra capacity gives headroom for an EV charger or additional appliances.