What Wire Size for 20 Amps?

Copper Wire
12 AWG
2.0525 mm · 3.3088 mm²
Aluminum Wire
10 AWG
2.5882 mm · 5.2612 mm²
Breaker: 20A · Based on NEC Table 310.16 (75°C insulation)

Common Uses for 20A Circuits

Kitchen, bathroom, garage circuits

12 AWG Copper — Key Specs

Diameter2.0525 mm (0.080808")
Area3.3088 mm²
Resistance at 20°C5.2104 Ω/km
Weight29.647 kg/km
Ampacity (75°C)25 A

Important: For long wire runs, you may need to upsize the wire to compensate for voltage drop. NEC recommends keeping voltage drop under 3% for branch circuits. Use our voltage drop calculator to check.

NEC 240.4(D) — why 12 AWG and not something smaller

NEC Table 310.16 rates 12 AWG copper at 25 A at 75°C, which looks like more headroom than a 20A circuit needs. It is not usable headroom. NEC 240.4(D), the small-conductor rule, caps the overcurrent device on 12 AWG copper at 20 A regardless of what the ampacity table says. The same applies to aluminum: 10 AWG aluminum shows 30 A in Table 310.16 but is capped at 25 A by 240.4(D).

This is why 12 AWG is the answer for a 20A circuit and why the next size down is not: the smaller conductor’s own 240.4(D) cap falls below 20 A. Any calculator that reads Table 310.16 without applying 240.4(D) will hand you an undersized, code-violating conductor.

The rule covers 18 through 10 AWG copper and 12 through 10 AWG aluminum. NEC 240.4(E) and 240.4(G) carve out narrow exceptions — tap conductors, motor circuits, air-conditioning equipment, and welders are sized under their own articles instead. See the full table on the wire size calculator.

Voltage Drop by Distance — 12 AWG Copper at 20A

One-way run Drop % of 120V Verdict
25 ft1.59 V1.3%Within the 3% branch-circuit target
50 ft3.18 V2.6%Within the 3% branch-circuit target
75 ft4.76 V4.0%Over 3% — upsize one gauge
100 ft6.35 V5.3%Over 5% — upsize two or more gauges
150 ft9.53 V7.9%Over 5% — upsize two or more gauges
200 ft12.70 V10.6%Over 5% — upsize two or more gauges
Single-phase, 120V, full 20A load, 1.5881 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. Voltage drop is a performance recommendation, not a code requirement — but exceeding it causes dim lights, slow motor starts, and wasted energy.

Related Appliance Guides

Related

Wire types and insulation ratings → 20 amp breaker — wire, ground and load → NEC Table 250.122 — ground wire size → 12 AWG full specifications → Full AWG chart → Wire size calculator → Ampacity tables →