WireSizing
Wire gauge reference & calculator

What Wire Size for 20 Amps?

Copper Wire
12 AWG
2.0525 mm · 3.3088 mm²
Aluminum Wire
10 AWG
2.5882 mm · 5.2612 mm²
Breaker: 20A · Based on NEC Table 310.16, 60°C column (the NEC 110.14(C) default at 100A or less)

20-Amp Wire Size by Termination Rating

RuleCopperAluminum
60°C column — NM-B cable, or any termination not marked 75°C12 AWG10 AWG
75°C column — THHN/THWN-2 with 75°C-rated breaker and lugs12 AWG10 AWG

Most breakers and panelboards rated 100A or less are listed 60/75°C, but NM-B cable is always limited to the 60°C column (NEC 334.80). When in doubt, use the 60°C answer.

Common Uses for 20A Circuits

Kitchen, bathroom, garage circuits

12 AWG Copper — Key Specs

Diameter2.0525 mm (0.080808")
Area3.3088 mm²
Resistance at 20°C5.2104 Ω/km
Weight29.647 kg/km
Ampacity (75°C)25 A

Important: For long wire runs, you may need to upsize the wire to compensate for voltage drop. NEC recommends keeping voltage drop under 3% for branch circuits. Use our voltage drop calculator to check.

NEC 240.4(D) — why 12 AWG and not something smaller

NEC Table 310.16 rates 12 AWG copper at 25 A at 75°C, which looks like more headroom than a 20A circuit needs. It is not usable headroom. NEC 240.4(D), the small-conductor rule, caps the overcurrent device on 12 AWG copper at 20 A regardless of what the ampacity table says. The same applies to aluminum: 10 AWG aluminum shows 30 A in Table 310.16 but is capped at 25 A by 240.4(D).

This is why 12 AWG is the answer for a 20A circuit and why the next size down is not: the smaller conductor’s own 240.4(D) cap falls below 20 A. Any calculator that reads Table 310.16 without applying 240.4(D) will hand you an undersized, code-violating conductor.

The rule covers 18 through 10 AWG copper and 12 through 10 AWG aluminum. NEC 240.4(E) and 240.4(G) carve out narrow exceptions — tap conductors, motor circuits, air-conditioning equipment, and welders are sized under their own articles instead. See the full table on the wire size calculator.

Voltage Drop by Distance — 12 AWG Copper at 20A

One-way run Drop % of 120V Verdict
25 ft1.98 V0.8%Within the 3% branch-circuit target
50 ft3.96 V1.7%Within the 3% branch-circuit target
75 ft5.94 V2.5%Within the 3% branch-circuit target
100 ft7.92 V3.3%Over 3% — upsize one gauge
150 ft11.88 V5.0%Over 3% — upsize one gauge
200 ft15.84 V6.6%Over 5% — upsize at least two gauges
Single-phase, 120V, full 20A load, 1.98 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. Voltage drop is a performance recommendation, not a code requirement — but exceeding it causes dim lights, slow motor starts, and wasted energy.

Related Appliance Guides

Frequently Asked Questions

What wire size do I need for 20 amps?

Using the 60°C column of NEC Table 310.16, which NEC 110.14(C) requires by default for circuits of 100A or less and always for NM-B cable, a 20-amp circuit needs 12 AWG copper or 10 AWG aluminum. NEC 240.4(D) sets the minimum here: 12 AWG copper may not be protected above 20A.

What breaker do I need for 20 amps?

A 20-amp circuit uses a 20A single-pole circuit breaker. The breaker protects the 12 AWG copper (or 10 AWG aluminum) wire from overload. Double-pole breakers are used for 240V circuits and occupy two slots in the panel.

Can I use 14 AWG wire on a 20-amp circuit?

No — NEC prohibits using 14 AWG wire on a 20-amp breaker. 14 AWG is rated for 15A maximum. Always use 12 AWG copper (or 10 AWG aluminum) for any 20-amp circuit.

What requires a dedicated 20-amp circuit?

NEC 210.11(C) requires at least two 20A small-appliance circuits for kitchen and dining countertop receptacles, at least one 20A circuit for bathroom receptacles, one 20A laundry circuit, and (since 2020) at least one 20A circuit for garage receptacles. The NEC does not require dedicated circuits for refrigerators, dishwashers or microwaves, although manufacturer instructions and local codes often do.

Wire size for other amperages

Related

Wire types and insulation ratings → 20 amp breaker — wire, ground and load → NEC Table 250.122 — ground wire size → 12 AWG full specifications → Full AWG chart → Wire size calculator → Ampacity tables →