What Wire Size for 80 Amps?

Copper Wire
4 AWG
5.1894 mm · 21.1506 mm²
Aluminum Wire
2 AWG
6.5437 mm · 33.6308 mm²
Breaker: 80A · Based on NEC Table 310.16, 75°C column (needs 75°C-rated terminations)

80-Amp Wire Size by Termination Rating

RuleCopperAluminum
60°C column — NM-B cable, or any termination not marked 75°C3 AWG1 AWG
75°C column — THHN/THWN-2 with 75°C-rated breaker and lugs4 AWG2 AWG

Most breakers and panelboards rated 100A or less are listed 60/75°C, but NM-B cable is always limited to the 60°C column (NEC 334.80). When in doubt, use the 60°C answer.

Common Uses for 80A Circuits

Large sub-panels, industrial feeders

4 AWG Copper — Key Specs

Diameter5.1894 mm (0.204307")
Area21.1506 mm²
Resistance at 20°C0.8151 Ω/km
Weight189.51 kg/km
Ampacity (75°C)85 A

Important: For long wire runs, you may need to upsize the wire to compensate for voltage drop. NEC recommends keeping voltage drop under 3% for branch circuits. Use our voltage drop calculator to check.

Voltage Drop by Distance — 4 AWG Copper at 80A

One-way run Drop % of 240V Verdict
25 ft1.23 V0.5%Within the 3% branch-circuit target
50 ft2.46 V1.0%Within the 3% branch-circuit target
75 ft3.70 V1.5%Within the 3% branch-circuit target
100 ft4.93 V2.1%Within the 3% branch-circuit target
150 ft7.39 V3.1%Over 3% — upsize one gauge
200 ft9.86 V4.1%Over 3% — upsize one gauge
Single-phase, 240V, full 80A load, 0.308 Ω/1000 ft DC resistance (NEC Chapter 9, Table 8) at 75°C terminations. NEC 210.19(A) Informational Note recommends keeping branch-circuit drop at or below 3%, and 5% total across feeder plus branch circuit. Voltage drop is a performance recommendation, not a code requirement — but exceeding it causes dim lights, slow motor starts, and wasted energy.

Aluminum Feeder Specifications

Aluminum has about 61% of copper’s conductivity, so a 80A feeder that takes 4 AWG copper needs 2 AWG aluminum — typically one to two gauge sizes larger.

Aluminum conductor2 AWG
Ampacity (75°C, Table 310.16)90 A
Copper equivalent4 AWG (85 A)
Resistance0.2402 Ω/1000 ft
Voltage drop at 100 ft, 80A5.10 V (2.1% of 240V)

Installing aluminum correctly

  • Modern aluminum building wire must be AA-8000 series alloy (NEC 310.14(A)(1)). The 1960s-era AA-1350 alloy behind aluminum’s bad reputation is no longer permitted for branch circuits.
  • Terminate only on lugs and breakers marked AL/CU or AL9CU. Copper-only terminals are the most common failure point.
  • Apply an antioxidant compound to the stripped conductor before landing it, unless the termination is listed as not requiring it.
  • Torque every connection to the manufacturer’s value with a calibrated torque tool — NEC 110.14(D) makes this mandatory. Loose aluminum terminations are the primary cause of feeder failures.
  • Aluminum runs roughly half the weight and a third to half the cost of copper at feeder sizes, which is why it dominates service entrance and sub-panel feeders.

Frequently Asked Questions

What wire size do I need for 80 amps?

Using the 60°C column of NEC Table 310.16, which NEC 110.14(C) requires by default for circuits of 100A or less and always for NM-B cable, a 80-amp circuit needs 3 AWG copper or 1 AWG aluminum. With THHN/THWN-2 conductors and breakers and lugs rated 75°C, 4 AWG copper or 2 AWG aluminum is permitted.

What breaker do I need for 80 amps?

A 80-amp circuit uses a 80A double-pole circuit breaker. The breaker protects the 4 AWG copper (or 2 AWG aluminum) wire from overload. Double-pole breakers are used for 240V circuits and occupy two slots in the panel.

What wire size for an 80-amp sub-panel?

An 80-amp sub-panel feeder needs 4 AWG copper or 2 AWG aluminum with 75°C-rated terminations, or 3 AWG copper or 1 AWG aluminum if the 60°C column applies. This suits a large detached garage, workshop or accessory dwelling unit (ADU).

Can I use 4 AWG aluminum wire for an 80-amp circuit?

No. 4 AWG aluminum is rated 65A at 75°C and 55A at 60°C per NEC Table 310.16, both below 80A. Use 2 AWG aluminum (90A at 75°C) or 1 AWG aluminum if the 60°C column applies, or 4 AWG copper (85A at 75°C).