4/0 AWG Wire

4/0 AWG (American Wire Gauge) wire specifications: 11.684 mm diameter, 107.2193 mm² area, 230A ampacity (copper, 75°C). Resistance, weight, and common uses.

Diameter
11.684 mm
0.46"
Area
107.2193 mm²
211,600 cmil
Ampacity (Cu)
230A
75°C insulation
Resistance (Cu)
0.1608
Ω/km at 20°C

4/0 AWG — Complete Specifications

Diameter11.684 mm · 0.46" · 460.0 mils
Cross-sectional area107.2193 mm² · 211,600 circular mils
Resistance (copper, 20°C)0.1608 Ω/km · 0.049 Ω/1000ft
Resistance (aluminum, 20°C)0.2636 Ω/km · 0.0803 Ω/1000ft
Ampacity — copper 60°C195 A
Ampacity — copper 75°C230 A
Ampacity — copper 90°C260 A
Ampacity — aluminum 75°C180 A
Weight (copper)960.685 kg/km · 645.55 lbs/1000ft
Weight (aluminum)289.492 kg/km · 194.529 lbs/1000ft
Closest IEC 60228 size120 mm²
Skin depth at 60 Hz8.531 mm

Common Uses for 4/0 AWG Wire

Compatible Insulation Types

TypeTemperatureDescription
THHN/THWN-2 90°C dry / 75°C wet Most common for building wire
XHHW-2 90°C dry and wet Cross-linked polyethylene, moisture resistant
USE-2 90°C Underground service entrance
NM-B (Romex) 90°C Non-metallic sheathed cable for residential
UF-B 60°C Underground feeder, direct burial

Frequently Asked Questions

What is 4/0 AWG wire used for?

4/0 AWG copper is commonly used for 200A services and feeders where extra capacity or lower voltage drop is wanted (Table 310.16 alone needs only 3/0 copper at 200A). NEC Table 310.16 rates it 230A at 75°C. It measures 11.684 mm in diameter with a 107 mm² cross-section.

What is the ampacity of 4/0 AWG wire?

Per NEC Table 310.16 (30°C ambient, no more than three current-carrying conductors), 4/0 AWG copper is rated 195A at 60°C, 230A at 75°C and 260A at 90°C. 4/0 AWG aluminum is rated 150A, 180A and 205A in the same columns. Above 100A, NEC 110.14(C) allows the 75°C column when terminations are rated 75°C.

Is 4/0 AWG wire available in aluminum?

Yes. 4/0 AWG aluminum is rated 180A at 75°C versus 230A for copper. Aluminum at this size is common for feeders, subpanels and service conductors (SER, USE-2, XHHW-2). Use AL-rated lugs, torque to the manufacturer’s spec and apply antioxidant compound where required.

4/0 AWG voltage drop by distance

Explore

Conduit fill charts → Wire types and insulation ratings → Full AWG chart → Wire size calculator → AWG to mm² converter → Ampacity tables → Wire materials →