20 HP Motor — Full-Load Amps

Full-load ampere values for a 20-horsepower motor at every standard voltage and phase configuration listed in the NEC.

Three-Phase Induction (Table 430.250)

Voltage Full-Load Amps
115 V—
200 V62.1
208 V59.4
230 V54
460 V27
575 V22
2300 V—

DC (Table 430.247)

Voltage Full-Load Amps
90 V—
120 V—
180 V—
240 V72
500 V34
550 V31

Two-Phase 4-Wire (Table 430.249)

Voltage Full-Load Amps
115 V—
230 V47
460 V23
575 V19
2300 V—
← 15 HP 25 HP →

Frequently Asked Questions

How many amps does a 20 HP motor draw?

The NEC tables list the full-load current for a 20 HP motor at each standard voltage and phase configuration. These are design values for sizing conductors and protection, not nameplate ratings. See the table above for all voltages.

What size wire do I need for a 20 HP motor?

Size the branch-circuit conductors at 125% of the table FLA (NEC 430.22). Look up the FLA for your voltage above, multiply by 1.25, then find that ampacity in the wire size tables.