WireSizing
Wire gauge reference & calculator

125 HP Motor — Full-Load Amps

Full-load ampere values for a 125-horsepower motor at every standard voltage and phase configuration listed in the NEC.

Three-Phase Induction (Table 430.250)

Voltage Full-Load Amps
115 V—
200 V359
208 V343
230 V312
460 V156
575 V125
2300 V31

DC (Table 430.247)

Voltage Full-Load Amps
90 V—
120 V—
180 V—
240 V425
500 V205
550 V185

Two-Phase 4-Wire (Table 430.249)

Voltage Full-Load Amps
115 V—
230 V270
460 V135
575 V108
2300 V28
← 100 HP 150 HP →

Frequently Asked Questions

How many amps does a 125 HP motor draw?

The NEC tables list the full-load current for a 125 HP motor at each standard voltage and phase configuration. These are design values for sizing conductors and protection, not nameplate ratings. See the table above for all voltages.

What size wire do I need for a 125 HP motor?

Size the branch-circuit conductors at 125% of the table FLA (NEC 430.22). Look up the FLA for your voltage above, multiply by 1.25, then find that ampacity in the wire size tables.

Related

← All motor FLA tables AWG wire chart → Breaker size charts →

WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.