Full-load ampere values for a 150-horsepower motor at every standard voltage and phase configuration listed in the NEC.
| Voltage | Full-Load Amps |
|---|---|
| 115 V | — |
| 200 V | 414 |
| 208 V | 396 |
| 230 V | 360 |
| 460 V | 180 |
| 575 V | 144 |
| 2300 V | 37 |
| Voltage | Full-Load Amps |
|---|---|
| 90 V | — |
| 120 V | — |
| 180 V | — |
| 240 V | 506 |
| 500 V | 246 |
| 550 V | 222 |
| Voltage | Full-Load Amps |
|---|---|
| 115 V | — |
| 230 V | 312 |
| 460 V | 156 |
| 575 V | 125 |
| 2300 V | 32 |
The NEC tables list the full-load current for a 150 HP motor at each standard voltage and phase configuration. These are design values for sizing conductors and protection, not nameplate ratings. See the table above for all voltages.
Size the branch-circuit conductors at 125% of the table FLA (NEC 430.22). Look up the FLA for your voltage above, multiply by 1.25, then find that ampacity in the wire size tables.
WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.