WireSizing
Wire gauge reference & calculator

150 HP Motor — Full-Load Amps

Full-load ampere values for a 150-horsepower motor at every standard voltage and phase configuration listed in the NEC.

Three-Phase Induction (Table 430.250)

Voltage Full-Load Amps
115 V—
200 V414
208 V396
230 V360
460 V180
575 V144
2300 V37

DC (Table 430.247)

Voltage Full-Load Amps
90 V—
120 V—
180 V—
240 V506
500 V246
550 V222

Two-Phase 4-Wire (Table 430.249)

Voltage Full-Load Amps
115 V—
230 V312
460 V156
575 V125
2300 V32
← 125 HP 200 HP →

Frequently Asked Questions

How many amps does a 150 HP motor draw?

The NEC tables list the full-load current for a 150 HP motor at each standard voltage and phase configuration. These are design values for sizing conductors and protection, not nameplate ratings. See the table above for all voltages.

What size wire do I need for a 150 HP motor?

Size the branch-circuit conductors at 125% of the table FLA (NEC 430.22). Look up the FLA for your voltage above, multiply by 1.25, then find that ampacity in the wire size tables.

Related

← All motor FLA tables AWG wire chart → Breaker size charts →

WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.