200 HP Motor — Full-Load Amps

Full-load ampere values for a 200-horsepower motor at every standard voltage and phase configuration listed in the NEC.

Three-Phase Induction (Table 430.250)

Voltage Full-Load Amps
115 V—
200 V552
208 V528
230 V480
460 V240
575 V192
2300 V49

DC (Table 430.247)

Voltage Full-Load Amps
90 V—
120 V—
180 V—
240 V675
500 V330
550 V294

Two-Phase 4-Wire (Table 430.249)

Voltage Full-Load Amps
115 V—
230 V416
460 V208
575 V167
2300 V43
← 150 HP 250 HP →

Frequently Asked Questions

How many amps does a 200 HP motor draw?

The NEC tables list the full-load current for a 200 HP motor at each standard voltage and phase configuration. These are design values for sizing conductors and protection, not nameplate ratings. See the table above for all voltages.

What size wire do I need for a 200 HP motor?

Size the branch-circuit conductors at 125% of the table FLA (NEC 430.22). Look up the FLA for your voltage above, multiply by 1.25, then find that ampacity in the wire size tables.