Full-load ampere values for a 250-horsepower motor at every standard voltage and phase configuration listed in the NEC.

Three-Phase Induction (Table 430.250)

Voltage Full-Load Amps
115 V—
200 V—
208 V—
230 V—
460 V302
575 V242
2300 V60
← 200 HP 300 HP →

Frequently Asked Questions

How many amps does a 250 HP motor draw?

The NEC tables list the full-load current for a 250 HP motor at each standard voltage and phase configuration. These are design values for sizing conductors and protection, not nameplate ratings. See the table above for all voltages.

What size wire do I need for a 250 HP motor?

Size the branch-circuit conductors at 125% of the table FLA (NEC 430.22). Look up the FLA for your voltage above, multiply by 1.25, then find that ampacity in the wire size tables.