100 HP Motor — Full-Load Amps

Full-load ampere values for a 100-horsepower motor at every standard voltage and phase configuration listed in the NEC.

Three-Phase Induction (Table 430.250)

Voltage Full-Load Amps
115 V—
200 V285
208 V273
230 V248
460 V124
575 V99
2300 V26

DC (Table 430.247)

Voltage Full-Load Amps
90 V—
120 V—
180 V—
240 V341
500 V164
550 V148

Two-Phase 4-Wire (Table 430.249)

Voltage Full-Load Amps
115 V—
230 V218
460 V109
575 V87
2300 V23
← 75 HP 125 HP →

Frequently Asked Questions

How many amps does a 100 HP motor draw?

The NEC tables list the full-load current for a 100 HP motor at each standard voltage and phase configuration. These are design values for sizing conductors and protection, not nameplate ratings. See the table above for all voltages.

What size wire do I need for a 100 HP motor?

Size the branch-circuit conductors at 125% of the table FLA (NEC 430.22). Look up the FLA for your voltage above, multiply by 1.25, then find that ampacity in the wire size tables.