WireSizing
Wire gauge reference & calculator

Single-Phase AC Motor Full-Load Amps

NEC Table 430.248 — full-load current in amperes for single-phase ac motors at standard voltages.

HP 115 V 200 V 208 V 230 V
1/64.42.52.42.2
1/45.83.33.22.9
1/37.24.14.03.6
1/29.85.65.44.9
3/413.87.97.66.9
1169.28.88.0
1-1/22011.511.010
22413.813.212
33419.618.717
55632.230.828
7-1/28046.044.040
1010057.555.050
Source: NEC Table 430.248. A dash means the table does not list a value for that voltage.