WireSizing
Wire gauge reference & calculator

3/4 HP Motor — Full-Load Amps

Full-load ampere values for a 3/4-horsepower motor at every standard voltage and phase configuration listed in the NEC.

Single-Phase AC (Table 430.248)

Voltage Full-Load Amps
115 V13.8
200 V7.9
208 V7.6
230 V6.9

Three-Phase Induction (Table 430.250)

Voltage Full-Load Amps
115 V6.4
200 V3.7
208 V3.5
230 V3.2
460 V1.6
575 V1.3
2300 V—

DC (Table 430.247)

Voltage Full-Load Amps
90 V9.6
120 V7.6
180 V4.8
240 V3.8
500 V—
550 V—

Two-Phase 4-Wire (Table 430.249)

Voltage Full-Load Amps
115 V4.8
230 V2.4
460 V1.2
575 V1.0
2300 V—
← 1/2 HP 1 HP →

Frequently Asked Questions

How many amps does a 3/4 HP motor draw?

The NEC tables list the full-load current for a 3/4 HP motor at each standard voltage and phase configuration. These are design values for sizing conductors and protection, not nameplate ratings. See the table above for all voltages.

What size wire do I need for a 3/4 HP motor?

Size the branch-circuit conductors at 125% of the table FLA (NEC 430.22). Look up the FLA for your voltage above, multiply by 1.25, then find that ampacity in the wire size tables.

Related

← All motor FLA tables AWG wire chart → Breaker size charts →