WireSizing
Wire gauge reference & calculator

2 HP Motor — Full-Load Amps

Full-load ampere values for a 2-horsepower motor at every standard voltage and phase configuration listed in the NEC.

Single-Phase AC (Table 430.248)

Voltage Full-Load Amps
115 V24
200 V13.8
208 V13.2
230 V12

Three-Phase Induction (Table 430.250)

Voltage Full-Load Amps
115 V13.6
200 V7.8
208 V7.5
230 V6.8
460 V3.4
575 V2.7
2300 V—

DC (Table 430.247)

Voltage Full-Load Amps
90 V—
120 V17
180 V10.8
240 V8.5
500 V—
550 V—

Two-Phase 4-Wire (Table 430.249)

Voltage Full-Load Amps
115 V11.8
230 V5.9
460 V3.0
575 V2.4
2300 V—
← 1-1/2 HP 3 HP →

Frequently Asked Questions

How many amps does a 2 HP motor draw?

The NEC tables list the full-load current for a 2 HP motor at each standard voltage and phase configuration. These are design values for sizing conductors and protection, not nameplate ratings. See the table above for all voltages.

What size wire do I need for a 2 HP motor?

Size the branch-circuit conductors at 125% of the table FLA (NEC 430.22). Look up the FLA for your voltage above, multiply by 1.25, then find that ampacity in the wire size tables.

Related

← All motor FLA tables AWG wire chart → Breaker size charts →

WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.