NEC Table 430.250 — full-load current in amperes for three-phase induction motors at standard voltages.
| HP | 115 V | 200 V | 208 V | 230 V | 460 V | 575 V | 2300 V |
|---|---|---|---|---|---|---|---|
| 1/2 | 4.4 | 2.5 | 2.4 | 2.2 | 1.1 | 0.9 | — |
| 3/4 | 6.4 | 3.7 | 3.5 | 3.2 | 1.6 | 1.3 | — |
| 1 | 8.4 | 4.8 | 4.6 | 4.2 | 2.1 | 1.7 | — |
| 1-1/2 | 12.0 | 6.9 | 6.6 | 6.0 | 3.0 | 2.4 | — |
| 2 | 13.6 | 7.8 | 7.5 | 6.8 | 3.4 | 2.7 | — |
| 3 | — | 11.0 | 10.6 | 9.6 | 4.8 | 3.9 | — |
| 5 | — | 17.5 | 16.7 | 15.2 | 7.6 | 6.1 | — |
| 7-1/2 | — | 25.3 | 24.2 | 22 | 11 | 9 | — |
| 10 | — | 32.2 | 30.8 | 28 | 14 | 11 | — |
| 15 | — | 48.3 | 46.2 | 42 | 21 | 17 | — |
| 20 | — | 62.1 | 59.4 | 54 | 27 | 22 | — |
| 25 | — | 78.2 | 74.8 | 68 | 34 | 27 | — |
| 30 | — | 92 | 88 | 80 | 40 | 32 | — |
| 40 | — | 120 | 114 | 104 | 52 | 41 | — |
| 50 | — | 150 | 143 | 130 | 65 | 52 | — |
| 60 | — | 177 | 169 | 154 | 77 | 62 | 16 |
| 75 | — | 221 | 211 | 192 | 96 | 77 | 20 |
| 100 | — | 285 | 273 | 248 | 124 | 99 | 26 |
| 125 | — | 359 | 343 | 312 | 156 | 125 | 31 |
| 150 | — | 414 | 396 | 360 | 180 | 144 | 37 |
| 200 | — | 552 | 528 | 480 | 240 | 192 | 49 |
| 250 | — | — | — | — | 302 | 242 | 60 |
| 300 | — | — | — | — | 361 | 289 | 72 |
| 350 | — | — | — | — | 414 | 336 | 83 |
| 400 | — | — | — | — | 477 | 382 | 95 |
| 450 | — | — | — | — | 515 | 412 | 103 |
| 500 | — | — | — | — | 590 | 472 | 118 |
WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.