50 HP Motor — Full-Load Amps

Full-load ampere values for a 50-horsepower motor at every standard voltage and phase configuration listed in the NEC.

Three-Phase Induction (Table 430.250)

Voltage Full-Load Amps
115 V—
200 V150
208 V143
230 V130
460 V65
575 V52
2300 V—

DC (Table 430.247)

Voltage Full-Load Amps
90 V—
120 V—
180 V—
240 V173
500 V83
550 V75

Two-Phase 4-Wire (Table 430.249)

Voltage Full-Load Amps
115 V—
230 V113
460 V56
575 V45
2300 V—
← 40 HP 60 HP →

Frequently Asked Questions

How many amps does a 50 HP motor draw?

The NEC tables list the full-load current for a 50 HP motor at each standard voltage and phase configuration. These are design values for sizing conductors and protection, not nameplate ratings. See the table above for all voltages.

What size wire do I need for a 50 HP motor?

Size the branch-circuit conductors at 125% of the table FLA (NEC 430.22). Look up the FLA for your voltage above, multiply by 1.25, then find that ampacity in the wire size tables.