WireSizing
Wire gauge reference & calculator

60 HP Motor — Full-Load Amps

Full-load ampere values for a 60-horsepower motor at every standard voltage and phase configuration listed in the NEC.

Three-Phase Induction (Table 430.250)

Voltage Full-Load Amps
115 V—
200 V177
208 V169
230 V154
460 V77
575 V62
2300 V16

DC (Table 430.247)

Voltage Full-Load Amps
90 V—
120 V—
180 V—
240 V206
500 V99
550 V90

Two-Phase 4-Wire (Table 430.249)

Voltage Full-Load Amps
115 V—
230 V133
460 V67
575 V53
2300 V14
← 50 HP 75 HP →

Frequently Asked Questions

How many amps does a 60 HP motor draw?

The NEC tables list the full-load current for a 60 HP motor at each standard voltage and phase configuration. These are design values for sizing conductors and protection, not nameplate ratings. See the table above for all voltages.

What size wire do I need for a 60 HP motor?

Size the branch-circuit conductors at 125% of the table FLA (NEC 430.22). Look up the FLA for your voltage above, multiply by 1.25, then find that ampacity in the wire size tables.

Related

← All motor FLA tables AWG wire chart → Breaker size charts →

WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.