WireSizing
Wire gauge reference & calculator

95 mm² Wire

95 mm² metric wire specifications (IEC 60228): 10.998 mm diameter, 182A ampacity (copper, IEC 60364-5-52 method A1, PVC, 2 loaded), closest AWG equivalent is 3/0. Resistance, weight, and common uses.

Size
95 mm²
IEC 60228
Diameter
10.998 mm
Ampacity (Cu)
182A
≈ AWG
3/0

95 mm² — Complete Specifications

Cross-sectional area95 mm²
Diameter (solid equivalent)10.998 mm
Closest AWG equivalent3/0 AWG
Ampacity (copper, IEC 60364-5-52 method A1, PVC, 2 loaded)182 A
Ampacity (aluminum)142 A
Max resistance (copper, 20°C, IEC 60228 class 2)0.193 Ω/km
Max resistance (aluminium, 20°C, IEC 60228)0.32 Ω/km
Weight (copper)851.2 kg/km
Weight (aluminum)256.5 kg/km

Common Uses for 95 mm² Wire

Metric vs AWG

The IEC 60228 metric system specifies wire by cross-sectional area in mm², while AWG uses a gauge number system. The closest AWG equivalent to 95 mm² is 3/0 AWG, but they are not exactly the same size.

Metric sizes are standard in Europe, Asia, Australia, and most countries outside North America. When replacing or matching wire between systems, always verify the actual cross-sectional area rather than relying on approximate equivalents.

Frequently Asked Questions

What is 95 mm² wire used for?

95 mm² metric wire (IEC 60228) is rated 182A (copper, IEC 60364-5-52 method A1, PVC, 2 loaded) and is commonly used for high-current industrial supplies, main switchboard feeders, large transformer connections. Its diameter is 10.99 mm. The closest AWG equivalent is 3/0 AWG.

What AWG gauge is equivalent to 95 mm²?

95 mm² wire is approximately equivalent to 3/0 AWG in the American Wire Gauge system. Note that IEC and AWG sizes do not align exactly — when substituting, choose the AWG size with equal or greater cross-sectional area to ensure adequate ampacity.

Explore

Wire types and insulation ratings → All metric wire sizes → 3/0 AWG specifications → AWG to mm² converter → Wire size calculator →