2 AWG Wire for 100 Feet

Voltage drop analysis for 2 AWG copper wire over a 100-foot one-way run. See whether this gauge is suitable for your circuit at various loads and voltages.

Wire
2 AWG
Distance
100 ft
Resistance
0.1562
Ω/1000ft

Voltage Drop at 100 Feet

Single phase, copper conductor, one-way distance. ✅ = under 3%, ⚠️ = 3-5%, ❌ = over 5%

Load V-Drop @ 120V @ 240V
15A 0.47V ✅ 0.4% ✅ 0.2%
20A 0.62V ✅ 0.5% ✅ 0.3%
30A 0.94V ✅ 0.8% ✅ 0.4%
40A 1.25V ✅ 1.0% ✅ 0.5%
50A 1.56V ✅ 1.3% ✅ 0.7%

How Voltage Drop Is Calculated

Voltage drop for single-phase circuits: Vdrop = 2 × I × R × L

Where I = current in amps, R = resistance per foot (0.000156 Ω/ft for 2 AWG copper), and L = one-way distance (100 ft).

The factor of 2 accounts for both the supply and return conductors. NEC recommends a maximum 3% voltage drop for branch circuits and 5% for the total circuit (feeder + branch).

If voltage drop is too high: Use the next larger wire size. Going from 2 to 1 AWG roughly halves the voltage drop. Alternatively, for 120V loads, consider rewiring for 240V — same absolute drop but half the percentage.