THHN and THWN-2 Wire — Specifications, Ampacity and Uses

THHN is Thermoplastic High Heat-resistant Nylon-coated: a single insulated conductor rated 600 V and 90°C in dry locations. Nearly everything sold today is dual-marked THHN/THWN-2, which adds a 90°C wet rating. It is the default wire for anything pulled through conduit, and it is a conductor rather than a cable — it always needs a raceway.

THHN / THWN-2 — Specifications

PropertyValue
Voltage rating600 V
Temperature rating (dry)90°C (194°F)
Temperature rating (wet)75°C for THWN, 90°C for THWN-2
InsulationPVC (polyvinyl chloride) with an extruded nylon jacket
ConductorCopper or aluminum, solid through 10 AWG, stranded above
Sizes14 AWG through 1000 kcmil
NEC articleArticle 310, Table 310.4(A)
Ampacity column90°C for derating, but limited to 75°C at terminations
Direct burialNot permitted as a bare conductor — requires a raceway
Sunlight resistanceOnly where the marking says "sunlight resistant"
Specifications reflect the common commercial product and the governing NEC article. Always confirm the markings printed on the conductor or jacket, which are the authoritative statement of what a given reel is listed for.

THHN / THWN-2 Ampacity — Copper, 75°C Column of NEC Table 310.16

SizeAmpacity
14 AWG20 A
12 AWG25 A
10 AWG35 A
8 AWG50 A
6 AWG65 A
4 AWG85 A
3 AWG100 A
2 AWG115 A
1 AWG130 A
1/0 AWG150 A
2/0 AWG175 A
3/0 AWG200 A
4/0 AWG230 A
Copper conductors, 30°C ambient, not more than three current-carrying conductors. Correct for higher ambients and larger conductor counts with NEC Table 310.15. NEC 240.4(D) still caps 14, 12 and 10 AWG copper at 15, 20 and 30 A of overcurrent protection.

What the letters mean

T — thermoplastic insulation. H — heat resistant, good for 75°C. HH — high heat resistant, 90°C. W — suitable for wet locations. N — nylon outer jacket, which adds abrasion, oil and gas resistance and makes the wire slippery enough to pull easily.

The -2 suffix on THWN-2 means 90°C in both wet and dry locations. Plain THWN is only 75°C wet. Since almost all stock is dual-rated THHN/THWN-2, you get the 90°C wet rating whether you asked for it or not — but check the printing on the jacket rather than assuming.

Where THHN may and may not be used

THHN is a single conductor, not a cable assembly. It must be installed in a raceway — EMT, PVC, rigid metal, IMC, flexible metal conduit, or a wireway. It may not be run exposed, stapled to framing, or fished through walls the way NM-B cable can.

In wet locations, including any underground raceway, you need the THWN-2 rating. NEC 300.5(B) defines the interior of an underground raceway as a wet location, so plain THHN is not legal in buried PVC even though the pipe looks dry when you install it. Direct burial without a raceway is never permitted — that is what USE-2 and UF-B are for.

The 90°C rating is for derating, not for bigger breakers

The most common THHN mistake is loading a conductor to its 90°C ampacity. NEC 110.14(C) limits the circuit to the lowest temperature rating of any termination, and virtually every breaker and lug is listed at 75°C. So 12 AWG THHN is a 30 A conductor on paper, a 25 A conductor at the terminals, and a 20 A circuit once NEC 240.4(D) is applied.

What the 90°C rating actually buys you is headroom for derating. Nine conductors in a conduit derate to 70%: from the 90°C column that is 30 × 0.70 = 21 A, which still supports a 20 A circuit. From the 75°C column it would be 17.5 A and you would be forced up to 10 AWG.