5 AWG Wire

5 AWG (American Wire Gauge) wire specifications: 4.6213 mm diameter, 16.7732 mm² area. Resistance, weight, and common uses.

Diameter
4.6213 mm
0.181941"
Area
16.7732 mm²
33,102 cmil
Ampacity (Cu)
—
75°C insulation
Resistance (Cu)
1.0278
Ω/km at 20°C

5 AWG — Complete Specifications

Diameter4.6213 mm · 0.181941" · 181.94 mils
Cross-sectional area16.7732 mm² · 33,102 circular mils
Resistance (copper, 20°C)1.0278 Ω/km · 0.3133 Ω/1000ft
Resistance (aluminum, 20°C)1.6849 Ω/km · 0.5136 Ω/1000ft
Ampacity — copper 60°C— A
Ampacity — copper 75°C— A
Ampacity — copper 90°C— A
Ampacity — aluminum 75°C— A
Weight (copper)150.288 kg/km · 100.989 lbs/1000ft
Weight (aluminum)45.288 kg/km · 30.432 lbs/1000ft
Closest IEC 60228 size16 mm²
Skin depth at 60 Hz8.531 mm

Common Uses for 5 AWG Wire

Compatible Insulation Types

TypeTemperatureDescription
THHN/THWN-2 90°C dry / 75°C wet Most common for building wire
XHHW-2 90°C dry and wet Cross-linked polyethylene, moisture resistant
USE-2 90°C Underground service entrance
NM-B (Romex) 90°C Non-metallic sheathed cable for residential
UF-B 60°C Underground feeder, direct burial

Frequently Asked Questions

What is 5 AWG wire used for?

5 AWG copper (4.621 mm diameter, 16.77 mm²) is used for large feeder circuits typically rated around 55–65 A. Common applications include sub-panel feeds in commercial buildings, large motor branch circuits, and industrial control wiring where 6 AWG is too small but 4 AWG is oversized.

What is the ampacity of 5 AWG wire?

Per NEC Table 310.16, 5 AWG copper is rated 55 A at 60°C, 65 A at 75°C, and 75 A at 90°C. It is not subject to the fixed breaker limits in NEC 240.4(D), which only apply to 14–10 AWG. Standard overcurrent protection is typically a 60 A breaker per the next-size-up rule in NEC 240.4(B).