Side-by-side guides covering conductor materials, wire gauges, construction types, and insulation ratings. Each comparison includes NEC ampacity data and practical guidance on when to use which.

Wire Comparison Guides

Copper vs Aluminum

Compare conductivity, weight, cost, ampacity, and when to use each material.

Solid vs Stranded

Wire construction compared: flexibility, resistance, applications, and when to use each type.

12 AWG vs 14 AWG

Compare ampacity, NEC overcurrent rules, voltage drop, and when to use each gauge for residential circuits.

THHN vs XHHW

Insulation types compared: PVC/nylon vs XLPE, temperature ratings, wet location use, and NEC requirements.

Quick Comparison

PropertyCopperAluminum (EC-1350)
Conductivity100% IACS61% IACS
Resistivity at 20°C1.72 × 10⁻⁸ Ω·m2.83 × 10⁻⁸ Ω·m
Density8,960 kg/m³2,700 kg/m³
Size for 100A (75°C)3 AWG1 AWG
Size for 200A (75°C)3/0 AWG250 kcmil

Sizes from NEC Table 310.16 with 75°C terminations. Stranded conductors are required in raceways from 8 AWG up (NEC 310.3(C)); below that, solid 14–10 AWG is standard in NM-B cable.

Which should you choose?

For 15–30A branch circuits, use copper: small aluminum branch wiring has a poor track record at connections, and copper devices are cheaper and easier to find. For feeders and services of 60A and up, aluminum (AA-8000 or 1350 alloy) with AL/CU-rated lugs saves a large share of the cost and weight. Choose stranded conductors for anything pulled through conduit at 8 AWG and larger, for cords, and for anything that moves; solid wire is fine for 14–10 AWG cable in walls.