Allowable ampacities of single insulated conductors rated 150°C through 250°C in free air, based on ambient temperature of 40°C (104°F). NEC 2023.
| Wire size | 150°C | 200°C | 250°C (Nickel) |
|---|---|---|---|
| 14 AWG | 46 | 54 | 59 |
| 12 AWG | 60 | 68 | 78 |
| 10 AWG | 80 | 90 | 107 |
| 8 AWG | 106 | 124 | 142 |
| 6 AWG | 155 | 165 | 205 |
| 4 AWG | 190 | 220 | 278 |
| 3 AWG | 214 | 252 | 327 |
| 2 AWG | 255 | 293 | 381 |
| 1 AWG | 293 | 344 | 440 |
| 1/0 AWG | 339 | 399 | 532 |
| 2/0 AWG | 390 | 467 | 591 |
| 3/0 AWG | 451 | 546 | 708 |
| 4/0 AWG | 529 | 629 | 830 |
| Wire size | 150°C (amps) |
|---|---|
| 12 AWG | 47 |
| 10 AWG | 63 |
| 8 AWG | 83 |
| 6 AWG | 112 |
| 4 AWG | 148 |
| 3 AWG | 170 |
| 2 AWG | 198 |
| 1 AWG | 228 |
| 1/0 AWG | 263 |
| 2/0 AWG | 305 |
| 3/0 AWG | 351 |
| 4/0 AWG | 411 |
WireSizing.com is an independent reference. NEC® is a registered trademark of the NFPA. Values shown are commonly published engineering data; always confirm against the edition adopted in your jurisdiction and consult a licensed electrician.