4" EMT Conduit Fill Chart

14 AWG THHN
608
conductors max
12 AWG THHN
443
conductors max
10 AWG THHN
279
conductors max
Usable area at 40% fill: 5.901 in² · NEC Chapter 9, Tables 1, 4 and 5

About EMT (Electrical Metallic Tubing)

Thin-wall steel tubing, the most common raceway in commercial interiors and exposed residential work. Joined with set-screw or compression couplings, never threaded. Trade size 4" is covered by NEC Article 358, and its internal dimensions come from NEC Chapter 9, Table 4.

4" EMT — Internal Area & Fill Limits

Trade size4"
Total internal area (100%)14.753 in²
1 conductor (53%)7.819 in²
2 conductors (31%)4.573 in²
Over 2 conductors (40%)5.901 in²

4" EMT — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.0097608
120.0133443
100.0211279
80.0366161
60.0507116
40.082471
30.097360
20.115850
10.156237
1/00.185531
2/00.222326
3/00.267922
4/00.323718
250 kcmil0.397014
300 kcmil0.460812
350 kcmil0.524211
400 kcmil0.586310
500 kcmil0.70738
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type, which is the condition NEC Annex C tables are built on. Mix sizes or insulations and you must add the individual areas by hand against the fill area above.

4" EMT — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.0139424
120.0181326
100.0243242
80.0437135
60.0590100
40.081472
30.096261
20.114651
10.153438
1/00.182532
2/00.219026
3/00.264222
4/00.319718
250 kcmil0.390415
350 kcmil0.515311
500 kcmil0.69848
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. From 4 AWG up they are slightly smaller. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down — you cannot install a fraction of a wire.

Max conductors = floor( conduit area × fill % ÷ conductor area )

For 4" EMT with 12 AWG THHN: floor( 14.753 × 0.40 ÷ 0.0133 ) = 443 conductors

The three percentages in NEC Chapter 9, Table 1 are not arbitrary. A single conductor gets 53% because it can be pulled straight down the middle. Exactly two conductors get only 31% because two circles inside a circle waste the most space. Three or more conductors nest efficiently again, so the limit rises to 40%.

Fill is only half the job. Once you have more than three current-carrying conductors in the same raceway, NEC 310.15(C)(1) also derates their ampacity — 80% for 4–6 conductors, 70% for 7–9, 50% for 10–20. A conduit can be legally filled and still leave your conductors undersized for the load. See NEC Table 310.15 for the full derating factors.

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4 — and no ampacity derating applies to it. For 4" EMT that raises the usable area from 5.901 in² to 8.852 in².