WireSizing
Wire gauge reference & calculator

4" Rigid (RMC) Conduit Fill Chart

14 AWG THHN
531
conductors max
12 AWG THHN
387
conductors max
10 AWG THHN
244
conductors max
Usable area at 40% fill: 5.153 in² · NEC Chapter 9, Tables 1, 4 and 5

About Rigid Metal Conduit (RMC)

Heavy-wall threaded steel conduit — the thickest and strongest raceway in the NEC. Used for service masts, hazardous locations, and anywhere physical damage is likely. Trade size 4" is covered by NEC Article 344, and its internal dimensions come from NEC Chapter 9, Table 4.

4" Rigid (RMC) — Internal Area & Fill Limits

Trade size4"
Total internal area (100%)12.882 in²
1 conductor (53%)6.828 in²
2 conductors (31%)3.994 in²
Over 2 conductors (40%)5.153 in²

4" Rigid (RMC) — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.0097531
120.0133387
100.0211244
80.0366140
60.0507101
40.082462
30.097352
20.115844
10.156232
1/00.185527
2/00.222323
3/00.267919
4/00.323715
250 kcmil0.397012
300 kcmil0.460811
350 kcmil0.52429
400 kcmil0.58638
500 kcmil0.70737
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type, which is the condition NEC Annex C tables are built on. Mix sizes or insulations and you must add the individual areas by hand against the fill area above.

4" Rigid (RMC) — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.0139370
120.0181284
100.0243212
80.0437117
60.059087
40.081463
30.096253
20.114644
10.153433
1/00.182528
2/00.219023
3/00.264219
4/00.319716
250 kcmil0.390413
350 kcmil0.51539
500 kcmil0.69847
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. From 4 AWG up they are slightly smaller. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down — you cannot install a fraction of a wire.

Max conductors = floor( conduit area × fill % ÷ conductor area )

For 4" Rigid (RMC) with 12 AWG THHN: floor( 12.882 × 0.40 ÷ 0.0133 ) = 387 conductors

The three percentages in NEC Chapter 9, Table 1 are not arbitrary. A single conductor gets 53% because it can be pulled straight down the middle. Exactly two conductors get only 31% because two circles inside a circle waste the most space. Three or more conductors nest efficiently again, so the limit rises to 40%.

Fill is only half the job. Once you have more than three current-carrying conductors in the same raceway, NEC 310.15(C)(1) also derates their ampacity — 80% for 4–6 conductors, 70% for 7–9, 50% for 10–20. A conduit can be legally filled and still leave your conductors undersized for the load. See NEC Table 310.15 for the full derating factors.

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4 — and no ampacity derating applies to it. For 4" Rigid (RMC) that raises the usable area from 5.153 in² to 7.729 in².

Other Rigid (RMC) Sizes

4" in Other Conduit Types

Related

Conduit fill calculator → All conduit fill charts → THHN / THWN wire specifications → NEC Table 310.15 derating factors → Ampacity tables →