4" PVC Schedule 80 Conduit Fill Chart

14 AWG THHN
464
conductors max
12 AWG THHN
338
conductors max
10 AWG THHN
213
conductors max
Usable area at 40% fill: 4.503 in² · NEC Chapter 9, Tables 1, 4 and 5

About PVC Schedule 80 (Rigid PVC Conduit, Schedule 80)

Heavy-wall PVC required where conduit is exposed to physical damage, such as risers on poles and service masts. Same outside diameter as Schedule 40, so the thicker wall takes noticeably more room from the inside. Trade size 4" is covered by NEC Article 352, and its internal dimensions come from NEC Chapter 9, Table 4.

4" PVC Schedule 80 — Internal Area & Fill Limits

Trade size4"
Total internal area (100%)11.258 in²
1 conductor (53%)5.967 in²
2 conductors (31%)3.49 in²
Over 2 conductors (40%)4.503 in²

4" PVC Schedule 80 — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.0097464
120.0133338
100.0211213
80.0366123
60.050789
40.082454
30.097346
20.115839
10.156229
1/00.185524
2/00.222320
3/00.267917
4/00.323714
250 kcmil0.397011
300 kcmil0.46089
350 kcmil0.52428
400 kcmil0.58637
500 kcmil0.70736
600 kcmil0.86765
700 kcmil0.98874
750 kcmil1.04964
800 kcmil1.10854
900 kcmil1.23113
1000 kcmil1.34783
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

4" PVC Schedule 80 — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.0139324
120.0181248
100.0243185
80.0437103
60.059076
40.081455
30.096247
20.114639
10.153429
1/00.182524
2/00.219020
3/00.264217
4/00.319714
250 kcmil0.390411
300 kcmil0.453610
350 kcmil0.51668
400 kcmil0.57827
500 kcmil0.69846
600 kcmil0.87095
700 kcmil0.99234
750 kcmil1.05324
800 kcmil1.11224
900 kcmil1.23513
1000 kcmil1.35193
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 4" PVC Schedule 80 with 12 AWG THHN: 11.258 × 0.40 ÷ 0.0133 = 338.59 → 338 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 4" PVC Schedule 80 that raises the usable area from 4.503 in² to 6.755 in².

Other PVC Schedule 80 Sizes

4" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 4-inch PVC Schedule 80 conduit?

A 4-inch PVC Schedule 80 conduit has 11.258 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 4.503 in². That works out to 338 #12 THHN, 464 #14 THHN, 213 #10 THHN, or 123 #8 THHN conductors.

How many 12 AWG THHN wires fit in 4-inch PVC Schedule 80?

338 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 4-inch PVC Schedule 80 is 4.503 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.