WireSizing
Wire gauge reference & calculator

6" PVC Schedule 80 Conduit Fill Chart

14 AWG THHN
1055
conductors max
12 AWG THHN
770
conductors max
10 AWG THHN
485
conductors max
Usable area at 40% fill: 10.239 in² · NEC Chapter 9, Tables 1, 4 and 5

About PVC Schedule 80 (Rigid PVC Conduit, Schedule 80)

Heavy-wall PVC required where conduit is exposed to physical damage, such as risers on poles and service masts. Same outside diameter as Schedule 40, so the thicker wall takes noticeably more room from the inside. Trade size 6" is covered by NEC Article 352, and its internal dimensions come from NEC Chapter 9, Table 4.

6" PVC Schedule 80 — Internal Area & Fill Limits

Trade size6"
Total internal area (100%)25.598 in²
1 conductor (53%)13.567 in²
2 conductors (31%)7.935 in²
Over 2 conductors (40%)10.239 in²

6" PVC Schedule 80 — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.00971055
120.0133770
100.0211485
80.0366279
60.0507202
40.0824124
30.0973105
20.115888
10.156265
1/00.185555
2/00.222346
3/00.267938
4/00.323731
250 kcmil0.397025
300 kcmil0.460822
350 kcmil0.524219
400 kcmil0.586317
500 kcmil0.707314
600 kcmil0.867612
700 kcmil0.988710
750 kcmil1.04969
800 kcmil1.10859
900 kcmil1.23118
1000 kcmil1.34787
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

6" PVC Schedule 80 — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.0139736
120.0181565
100.0243421
80.0437234
60.0590173
40.0814125
30.0962106
20.114689
10.153466
1/00.182556
2/00.219046
3/00.264238
4/00.319732
250 kcmil0.390426
300 kcmil0.453622
350 kcmil0.516620
400 kcmil0.578217
500 kcmil0.698414
600 kcmil0.870911
700 kcmil0.992310
750 kcmil1.05329
800 kcmil1.11229
900 kcmil1.23518
1000 kcmil1.35197
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 6" PVC Schedule 80 with 12 AWG THHN: 25.598 × 0.40 ÷ 0.0133 = 769.86 → 770 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 6" PVC Schedule 80 that raises the usable area from 10.239 in² to 15.359 in².

Other PVC Schedule 80 Sizes

6" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 6-inch PVC Schedule 80 conduit?

A 6-inch PVC Schedule 80 conduit has 25.598 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 10.239 in². That works out to 770 #12 THHN, 1055 #14 THHN, 485 #10 THHN, or 279 #8 THHN conductors.

How many 12 AWG THHN wires fit in 6-inch PVC Schedule 80?

770 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 6-inch PVC Schedule 80 is 10.239 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.

Related

Conduit fill calculator → All conduit fill charts → Ampacity tables →