WireSizing
Wire gauge reference & calculator

1-1/2" PVC Schedule 80 Conduit Fill Chart

14 AWG THHN
70
conductors max
12 AWG THHN
51
conductors max
10 AWG THHN
32
conductors max
Usable area at 40% fill: 0.684 in² · NEC Chapter 9, Tables 1, 4 and 5

About PVC Schedule 80 (Rigid PVC Conduit, Schedule 80)

Heavy-wall PVC required where conduit is exposed to physical damage, such as risers on poles and service masts. Same outside diameter as Schedule 40, so the thicker wall takes noticeably more room from the inside. Trade size 1-1/2" is covered by NEC Article 352, and its internal dimensions come from NEC Chapter 9, Table 4.

1-1/2" PVC Schedule 80 — Internal Area & Fill Limits

Trade size1-1/2"
Total internal area (100%)1.711 in²
1 conductor (53%)0.907 in²
2 conductors (31%)0.53 in²
Over 2 conductors (40%)0.684 in²

1-1/2" PVC Schedule 80 — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.009770
120.013351
100.021132
80.036618
60.050713
40.08248
30.09737
20.11586
10.15624
1/00.18553
2/00.22233
3/00.26791
4/00.32371
250 kcmil0.39701
300 kcmil0.46081
350 kcmil0.52421
400 kcmil0.58631
500 kcmil0.70731
600 kcmil0.86761
700 kcmil0.9887—
750 kcmil1.0496—
800 kcmil1.1085—
900 kcmil1.2311—
1000 kcmil1.3478—
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

1-1/2" PVC Schedule 80 — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.013949
120.018138
100.024328
80.043715
60.059011
40.08148
30.09627
20.11466
10.15344
1/00.18253
2/00.21903
3/00.26422
4/00.31971
250 kcmil0.39041
300 kcmil0.45361
350 kcmil0.51661
400 kcmil0.57821
500 kcmil0.69841
600 kcmil0.87091
700 kcmil0.9923—
750 kcmil1.0532—
800 kcmil1.1122—
900 kcmil1.2351—
1000 kcmil1.3519—
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 1-1/2" PVC Schedule 80 with 12 AWG THHN: 1.711 × 0.40 ÷ 0.0133 = 51.46 → 51 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 1-1/2" PVC Schedule 80 that raises the usable area from 0.684 in² to 1.027 in².

Other PVC Schedule 80 Sizes

1-1/2" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 1-1/2-inch PVC Schedule 80 conduit?

A 1-1/2-inch PVC Schedule 80 conduit has 1.711 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 0.684 in². That works out to 51 #12 THHN, 70 #14 THHN, 32 #10 THHN, or 18 #8 THHN conductors.

How many 12 AWG THHN wires fit in 1-1/2-inch PVC Schedule 80?

51 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 1-1/2-inch PVC Schedule 80 is 0.684 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.

Related

Conduit fill calculator → All conduit fill charts → Ampacity tables →