Maximum number of THHN/THWN-2 conductors in PVC Schedule 80 (Rigid PVC Conduit, Schedule 80), trade sizes 1/2 inch through 6 inch. Internal areas from NEC Chapter 9, Table 4; fill limits from Table 1 (53% for one conductor, 31% for two, 40% for three or more). NEC Article 352.
| Trade size | 40% area (in²) | 14 | 12 | 10 | 8 | 6 | 4 | 2 | 1/0 | 2/0 | 4/0 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1/2" | 0.087 | 9 | 6 | 4 | 1 | 1 | 1 | — | — | — | — |
| 3/4" | 0.164 | 17 | 12 | 7 | 4 | 3 | 1 | 1 | 1 | — | — |
| 1" | 0.275 | 28 | 20 | 13 | 7 | 5 | 3 | 1 | 1 | 1 | 1 |
| 1-1/4" | 0.495 | 51 | 37 | 23 | 13 | 9 | 6 | 4 | 2 | 1 | 1 |
| 1-1/2" | 0.684 | 70 | 51 | 32 | 18 | 13 | 8 | 6 | 3 | 3 | 1 |
| 2" | 1.15 | 118 | 86 | 54 | 31 | 22 | 14 | 10 | 6 | 5 | 3 |
| 2-1/2" | 1.648 | 170 | 124 | 78 | 45 | 32 | 20 | 14 | 9 | 7 | 5 |
| 3" | 2.577 | 265 | 193 | 122 | 70 | 51 | 31 | 22 | 14 | 11 | 8 |
| 3-1/2" | 3.475 | 358 | 261 | 164 | 95 | 68 | 42 | 30 | 18 | 15 | 10 |
| 4" | 4.503 | 464 | 338 | 213 | 123 | 89 | 54 | 39 | 24 | 20 | 14 |
| 5" | 7.142 | 736 | 537 | 338 | 195 | 141 | 86 | 61 | 38 | 32 | 22 |
| 6" | 10.239 | 1055 | 770 | 485 | 279 | 202 | 124 | 88 | 55 | 46 | 31 |
Column headings are AWG conductor sizes, all THHN/THWN-2. A dash means the conductor does not fit even as a single conductor at the 53% limit.
Heavy-wall PVC required where conduit is exposed to physical damage, such as risers on poles and service masts. Same outside diameter as Schedule 40, so the thicker wall takes noticeably more room from the inside.