3-1/2" PVC Schedule 80 Conduit Fill Chart

14 AWG THHN
358
conductors max
12 AWG THHN
261
conductors max
10 AWG THHN
164
conductors max
Usable area at 40% fill: 3.475 in² · NEC Chapter 9, Tables 1, 4 and 5

About PVC Schedule 80 (Rigid PVC Conduit, Schedule 80)

Heavy-wall PVC required where conduit is exposed to physical damage, such as risers on poles and service masts. Same outside diameter as Schedule 40, so the thicker wall takes noticeably more room from the inside. Trade size 3-1/2" is covered by NEC Article 352, and its internal dimensions come from NEC Chapter 9, Table 4.

3-1/2" PVC Schedule 80 — Internal Area & Fill Limits

Trade size3-1/2"
Total internal area (100%)8.688 in²
1 conductor (53%)4.605 in²
2 conductors (31%)2.693 in²
Over 2 conductors (40%)3.475 in²

3-1/2" PVC Schedule 80 — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.0097358
120.0133261
100.0211164
80.036695
60.050768
40.082442
30.097335
20.115830
10.156222
1/00.185518
2/00.222315
3/00.267913
4/00.323710
250 kcmil0.39708
300 kcmil0.46087
350 kcmil0.52426
400 kcmil0.58636
500 kcmil0.70735
600 kcmil0.86764
700 kcmil0.98873
750 kcmil1.04963
800 kcmil1.10853
900 kcmil1.23113
1000 kcmil1.34781
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

3-1/2" PVC Schedule 80 — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.0139250
120.0181192
100.0243143
80.043779
60.059059
40.081442
30.096236
20.114630
10.153422
1/00.182519
2/00.219016
3/00.264213
4/00.319711
250 kcmil0.39049
300 kcmil0.45367
350 kcmil0.51666
400 kcmil0.57826
500 kcmil0.69845
600 kcmil0.87094
700 kcmil0.99233
750 kcmil1.05323
800 kcmil1.11223
900 kcmil1.23513
1000 kcmil1.35191
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 3-1/2" PVC Schedule 80 with 12 AWG THHN: 8.688 × 0.40 ÷ 0.0133 = 261.29 → 261 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 3-1/2" PVC Schedule 80 that raises the usable area from 3.475 in² to 5.213 in².

Other PVC Schedule 80 Sizes

3-1/2" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 3-1/2-inch PVC Schedule 80 conduit?

A 3-1/2-inch PVC Schedule 80 conduit has 8.688 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 3.475 in². That works out to 261 #12 THHN, 358 #14 THHN, 164 #10 THHN, or 95 #8 THHN conductors.

How many 12 AWG THHN wires fit in 3-1/2-inch PVC Schedule 80?

261 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 3-1/2-inch PVC Schedule 80 is 3.475 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.

Related

Conduit fill calculator → All conduit fill charts → Ampacity tables →