3-1/2" Flexible Metal (FMC) Conduit Fill Chart

14 AWG THHN
396
conductors max
12 AWG THHN
289
conductors max
10 AWG THHN
182
conductors max
Usable area at 40% fill: 3.848 in² · NEC Chapter 9, Tables 1, 4 and 5

About Flexible Metal (FMC) (Flexible Metal Conduit (FMC))

Spiral-wound interlocked steel or aluminum “Greenfield”. Used for short whips to motors, fixtures and equipment that vibrates or needs to move. Trade size 3-1/2" is covered by NEC Article 348, and its internal dimensions come from NEC Chapter 9, Table 4.

3-1/2" Flexible Metal (FMC) — Internal Area & Fill Limits

Trade size3-1/2"
Total internal area (100%)9.621 in²
1 conductor (53%)5.099 in²
2 conductors (31%)2.983 in²
Over 2 conductors (40%)3.848 in²

3-1/2" Flexible Metal (FMC) — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.0097396
120.0133289
100.0211182
80.0366105
60.050776
40.082446
30.097339
20.115833
10.156224
1/00.185520
2/00.222317
3/00.267914
4/00.323712
250 kcmil0.39709
300 kcmil0.46088
350 kcmil0.52427
400 kcmil0.58636
500 kcmil0.70735
600 kcmil0.86764
700 kcmil0.98874
750 kcmil1.04963
800 kcmil1.10853
900 kcmil1.23113
1000 kcmil1.34783
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

3-1/2" Flexible Metal (FMC) — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.0139277
120.0181212
100.0243158
80.043788
60.059065
40.081447
30.096240
20.114633
10.153425
1/00.182521
2/00.219017
3/00.264214
4/00.319712
250 kcmil0.390410
300 kcmil0.45368
350 kcmil0.51667
400 kcmil0.57826
500 kcmil0.69845
600 kcmil0.87094
700 kcmil0.99234
750 kcmil1.05323
800 kcmil1.11223
900 kcmil1.23513
1000 kcmil1.35193
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 3-1/2" Flexible Metal (FMC) with 12 AWG THHN: 9.621 × 0.40 ÷ 0.0133 = 289.35 → 289 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 3-1/2" Flexible Metal (FMC) that raises the usable area from 3.848 in² to 5.773 in².

Other Flexible Metal (FMC) Sizes

3-1/2" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 3-1/2-inch Flexible Metal Conduit conduit?

A 3-1/2-inch Flexible Metal Conduit conduit has 9.621 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 3.848 in². That works out to 289 #12 THHN, 396 #14 THHN, 182 #10 THHN, or 105 #8 THHN conductors.

How many 12 AWG THHN wires fit in 3-1/2-inch Flexible Metal Conduit?

289 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 3-1/2-inch Flexible Metal Conduit is 3.848 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.