2-1/2" Flexible Metal (FMC) Conduit Fill Chart

14 AWG THHN
202
conductors max
12 AWG THHN
147
conductors max
10 AWG THHN
93
conductors max
Usable area at 40% fill: 1.964 in² · NEC Chapter 9, Tables 1, 4 and 5

About Flexible Metal (FMC) (Flexible Metal Conduit (FMC))

Spiral-wound interlocked steel or aluminum “Greenfield”. Used for short whips to motors, fixtures and equipment that vibrates or needs to move. Trade size 2-1/2" is covered by NEC Article 348, and its internal dimensions come from NEC Chapter 9, Table 4.

2-1/2" Flexible Metal (FMC) — Internal Area & Fill Limits

Trade size2-1/2"
Total internal area (100%)4.909 in²
1 conductor (53%)2.602 in²
2 conductors (31%)1.522 in²
Over 2 conductors (40%)1.964 in²

2-1/2" Flexible Metal (FMC) — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.0097202
120.0133147
100.021193
80.036653
60.050738
40.082424
30.097320
20.115817
10.156212
1/00.185510
2/00.22239
3/00.26797
4/00.32376
250 kcmil0.39705
300 kcmil0.46084
350 kcmil0.52423
400 kcmil0.58633
500 kcmil0.70732
600 kcmil0.86761
700 kcmil0.98871
750 kcmil1.04961
800 kcmil1.10851
900 kcmil1.23111
1000 kcmil1.34781
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

2-1/2" Flexible Metal (FMC) — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.0139141
120.0181108
100.024381
80.043745
60.059033
40.081424
30.096220
20.114617
10.153413
1/00.182510
2/00.21909
3/00.26427
4/00.31976
250 kcmil0.39045
300 kcmil0.45364
350 kcmil0.51664
400 kcmil0.57823
500 kcmil0.69843
600 kcmil0.87091
700 kcmil0.99231
750 kcmil1.05321
800 kcmil1.11221
900 kcmil1.23511
1000 kcmil1.35191
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 2-1/2" Flexible Metal (FMC) with 12 AWG THHN: 4.909 × 0.40 ÷ 0.0133 = 147.64 → 147 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 2-1/2" Flexible Metal (FMC) that raises the usable area from 1.964 in² to 2.945 in².

Other Flexible Metal (FMC) Sizes

2-1/2" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 2-1/2-inch Flexible Metal Conduit conduit?

A 2-1/2-inch Flexible Metal Conduit conduit has 4.909 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 1.964 in². That works out to 147 #12 THHN, 202 #14 THHN, 93 #10 THHN, or 53 #8 THHN conductors.

How many 12 AWG THHN wires fit in 2-1/2-inch Flexible Metal Conduit?

147 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 2-1/2-inch Flexible Metal Conduit is 1.964 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.