2-1/2" Rigid (RMC) Conduit Fill Chart

14 AWG THHN
200
conductors max
12 AWG THHN
146
conductors max
10 AWG THHN
92
conductors max
Usable area at 40% fill: 1.946 in² · NEC Chapter 9, Tables 1, 4 and 5

About Rigid Metal Conduit (RMC)

Heavy-wall threaded steel conduit — the thickest and strongest raceway in the NEC. Used for service masts, hazardous locations, and anywhere physical damage is likely. Trade size 2-1/2" is covered by NEC Article 344, and its internal dimensions come from NEC Chapter 9, Table 4.

2-1/2" Rigid (RMC) — Internal Area & Fill Limits

Trade size2-1/2"
Total internal area (100%)4.866 in²
1 conductor (53%)2.579 in²
2 conductors (31%)1.508 in²
Over 2 conductors (40%)1.946 in²

2-1/2" Rigid (RMC) — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.0097200
120.0133146
100.021192
80.036653
60.050738
40.082423
30.097320
20.115816
10.156212
1/00.185510
2/00.22238
3/00.26797
4/00.32376
250 kcmil0.39704
300 kcmil0.46084
350 kcmil0.52423
400 kcmil0.58633
500 kcmil0.70732
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type, which is the condition NEC Annex C tables are built on. Mix sizes or insulations and you must add the individual areas by hand against the fill area above.

2-1/2" Rigid (RMC) — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.0139140
120.0181107
100.024380
80.043744
60.059032
40.081423
30.096220
20.114616
10.153412
1/00.182510
2/00.21908
3/00.26427
4/00.31976
250 kcmil0.39044
350 kcmil0.51533
500 kcmil0.69842
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. From 4 AWG up they are slightly smaller. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down — you cannot install a fraction of a wire.

Max conductors = floor( conduit area × fill % ÷ conductor area )

For 2-1/2" Rigid (RMC) with 12 AWG THHN: floor( 4.866 × 0.40 ÷ 0.0133 ) = 146 conductors

The three percentages in NEC Chapter 9, Table 1 are not arbitrary. A single conductor gets 53% because it can be pulled straight down the middle. Exactly two conductors get only 31% because two circles inside a circle waste the most space. Three or more conductors nest efficiently again, so the limit rises to 40%.

Fill is only half the job. Once you have more than three current-carrying conductors in the same raceway, NEC 310.15(C)(1) also derates their ampacity — 80% for 4–6 conductors, 70% for 7–9, 50% for 10–20. A conduit can be legally filled and still leave your conductors undersized for the load. See NEC Table 310.15 for the full derating factors.

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4 — and no ampacity derating applies to it. For 2-1/2" Rigid (RMC) that raises the usable area from 1.946 in² to 2.920 in².

Other Rigid (RMC) Sizes

2-1/2" in Other Conduit Types

Related

Conduit fill calculator → All conduit fill charts → THHN / THWN wire specifications → NEC Table 310.15 derating factors → Ampacity tables →