WireSizing
Wire gauge reference & calculator

3/4" Rigid (RMC) Conduit Fill Chart

14 AWG THHN
22
conductors max
12 AWG THHN
16
conductors max
10 AWG THHN
10
conductors max
Usable area at 40% fill: 0.220 in² · NEC Chapter 9, Tables 1, 4 and 5

About Rigid Metal Conduit (RMC)

Heavy-wall threaded steel conduit — the thickest and strongest raceway in the NEC. Used for service masts, hazardous locations, and anywhere physical damage is likely. Trade size 3/4" is covered by NEC Article 344, and its internal dimensions come from NEC Chapter 9, Table 4.

3/4" Rigid (RMC) — Internal Area & Fill Limits

Trade size3/4"
Total internal area (100%)0.549 in²
1 conductor (53%)0.291 in²
2 conductors (31%)0.170 in²
Over 2 conductors (40%)0.220 in²

3/4" Rigid (RMC) — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.009722
120.013316
100.021110
80.03666
60.05074
40.08242
30.09731
20.11581
10.15621
1/00.18551
2/00.22231
3/00.26791
4/00.3237—
250 kcmil0.3970—
300 kcmil0.4608—
350 kcmil0.5242—
400 kcmil0.5863—
500 kcmil0.7073—
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type, which is the condition NEC Annex C tables are built on. Mix sizes or insulations and you must add the individual areas by hand against the fill area above.

3/4" Rigid (RMC) — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.013915
120.018112
100.02439
80.04375
60.05903
40.08142
30.09621
20.11461
10.15341
1/00.18251
2/00.21901
3/00.26421
4/00.3197—
250 kcmil0.3904—
350 kcmil0.5153—
500 kcmil0.6984—
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. From 4 AWG up they are slightly smaller. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 3/4" Rigid (RMC) with 12 AWG THHN: 0.549 × 0.40 ÷ 0.0133 = 16.51 → 16 conductors

The three percentages in NEC Chapter 9, Table 1 are not arbitrary. A single conductor gets 53% because it can be pulled straight down the middle. Exactly two conductors get only 31% because two circles inside a circle waste the most space. Three or more conductors nest efficiently again, so the limit rises to 40%.

Fill is only half the job. Once you have more than three current-carrying conductors in the same raceway, NEC 310.15(C)(1) also derates their ampacity — 80% for 4–6 conductors, 70% for 7–9, 50% for 10–20. A conduit can be legally filled and still leave your conductors undersized for the load. See NEC Table 310.15 for the full derating factors.

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4 — and no ampacity derating applies to it. For 3/4" Rigid (RMC) that raises the usable area from 0.220 in² to 0.329 in².

Other Rigid (RMC) Sizes

3/4" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 3/4-inch Rigid (RMC) conduit?

A 3/4-inch Rigid (RMC) conduit has 0.549 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 0.220 in². That works out to 16 #12 THHN, 22 #14 THHN, 10 #10 THHN, or 6 #8 THHN conductors.

How many 12 AWG THHN wires fit in 3/4-inch Rigid (RMC)?

16 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 3/4-inch Rigid (RMC) is 0.220 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.

Does the equipment grounding conductor count toward conduit fill?

Yes. Every conductor in the raceway counts toward the cross-sectional fill calculation, including equipment grounding conductors and neutrals. Grounding conductors do not count as current-carrying conductors for the separate NEC 310.15(C)(1) derating calculation, but they still occupy space.

Related

Conduit fill calculator → All conduit fill charts → THHN / THWN wire specifications → NEC Table 310.15 derating factors → Ampacity tables →