3/4" Liquidtight (LFMC) Conduit Fill Chart

14 AWG THHN
22
conductors max
12 AWG THHN
16
conductors max
10 AWG THHN
10
conductors max
Usable area at 40% fill: 0.216 in² · NEC Chapter 9, Tables 1, 4 and 5

About Liquidtight (LFMC) (Liquidtight Flexible Metal Conduit (LFMC))

Flexible metal conduit with a sunlight- and oil-resistant thermoplastic jacket. The usual choice for outdoor equipment whips: air conditioners, pumps, rooftop units. Trade size 3/4" is covered by NEC Article 350, and its internal dimensions come from NEC Chapter 9, Table 4.

3/4" Liquidtight (LFMC) — Internal Area & Fill Limits

Trade size3/4"
Total internal area (100%)0.541 in²
1 conductor (53%)0.287 in²
2 conductors (31%)0.168 in²
Over 2 conductors (40%)0.216 in²

3/4" Liquidtight (LFMC) — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.009722
120.013316
100.021110
80.03666
60.05074
40.08242
30.09731
20.11581
10.15621
1/00.18551
2/00.22231
3/00.26791
4/00.3237—
250 kcmil0.3970—
300 kcmil0.4608—
350 kcmil0.5242—
400 kcmil0.5863—
500 kcmil0.7073—
600 kcmil0.8676—
700 kcmil0.9887—
750 kcmil1.0496—
800 kcmil1.1085—
900 kcmil1.2311—
1000 kcmil1.3478—
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

3/4" Liquidtight (LFMC) — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.013915
120.018112
100.02439
80.04375
60.05903
40.08142
30.09621
20.11461
10.15341
1/00.18251
2/00.21901
3/00.26421
4/00.3197—
250 kcmil0.3904—
300 kcmil0.4536—
350 kcmil0.5166—
400 kcmil0.5782—
500 kcmil0.6984—
600 kcmil0.8709—
700 kcmil0.9923—
750 kcmil1.0532—
800 kcmil1.1122—
900 kcmil1.2351—
1000 kcmil1.3519—
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 3/4" Liquidtight (LFMC) with 12 AWG THHN: 0.541 × 0.40 ÷ 0.0133 = 16.27 → 16 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 3/4" Liquidtight (LFMC) that raises the usable area from 0.216 in² to 0.325 in².

Other Liquidtight (LFMC) Sizes

3/4" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 3/4-inch Liquidtight Flexible Metal Conduit conduit?

A 3/4-inch Liquidtight Flexible Metal Conduit conduit has 0.541 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 0.216 in². That works out to 16 #12 THHN, 22 #14 THHN, 10 #10 THHN, or 6 #8 THHN conductors.

How many 12 AWG THHN wires fit in 3/4-inch Liquidtight Flexible Metal Conduit?

16 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 3/4-inch Liquidtight Flexible Metal Conduit is 0.216 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.

Related

Conduit fill calculator → All conduit fill charts → Ampacity tables →