WireSizing
Wire gauge reference & calculator

3/8" Liquidtight (LFMC) Conduit Fill Chart

14 AWG THHN
8
conductors max
12 AWG THHN
5
conductors max
10 AWG THHN
3
conductors max
Usable area at 40% fill: 0.077 in² · NEC Chapter 9, Tables 1, 4 and 5

About Liquidtight (LFMC) (Liquidtight Flexible Metal Conduit (LFMC))

Flexible metal conduit with a sunlight- and oil-resistant thermoplastic jacket. The usual choice for outdoor equipment whips: air conditioners, pumps, rooftop units. Trade size 3/8" is covered by NEC Article 350, and its internal dimensions come from NEC Chapter 9, Table 4.

3/8" Liquidtight (LFMC) — Internal Area & Fill Limits

Trade size3/8"
Total internal area (100%)0.192 in²
1 conductor (53%)0.102 in²
2 conductors (31%)0.06 in²
Over 2 conductors (40%)0.077 in²

3/8" Liquidtight (LFMC) — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.00978
120.01335
100.02113
80.03661
60.05071
40.08241
30.09731
20.1158—
10.1562—
1/00.1855—
2/00.2223—
3/00.2679—
4/00.3237—
250 kcmil0.3970—
300 kcmil0.4608—
350 kcmil0.5242—
400 kcmil0.5863—
500 kcmil0.7073—
600 kcmil0.8676—
700 kcmil0.9887—
750 kcmil1.0496—
800 kcmil1.1085—
900 kcmil1.2311—
1000 kcmil1.3478—
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

3/8" Liquidtight (LFMC) — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.01395
120.01814
100.02433
80.04371
60.05901
40.08141
30.09621
20.1146—
10.1534—
1/00.1825—
2/00.2190—
3/00.2642—
4/00.3197—
250 kcmil0.3904—
300 kcmil0.4536—
350 kcmil0.5166—
400 kcmil0.5782—
500 kcmil0.6984—
600 kcmil0.8709—
700 kcmil0.9923—
750 kcmil1.0532—
800 kcmil1.1122—
900 kcmil1.2351—
1000 kcmil1.3519—
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 3/8" Liquidtight (LFMC) with 12 AWG THHN: 0.192 × 0.40 ÷ 0.0133 = 5.77 → 5 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 3/8" Liquidtight (LFMC) that raises the usable area from 0.077 in² to 0.115 in².

Other Liquidtight (LFMC) Sizes

3/8" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 3/8-inch Liquidtight Flexible Metal Conduit conduit?

A 3/8-inch Liquidtight Flexible Metal Conduit conduit has 0.192 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 0.077 in². That works out to 5 #12 THHN, 8 #14 THHN, 3 #10 THHN, or 1 #8 THHN conductors.

How many 12 AWG THHN wires fit in 3/8-inch Liquidtight Flexible Metal Conduit?

5 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 3/8-inch Liquidtight Flexible Metal Conduit is 0.077 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.

Related

Conduit fill calculator → All conduit fill charts → Ampacity tables →