WireSizing
Wire gauge reference & calculator

3" Liquidtight (LFMC) Conduit Fill Chart

14 AWG THHN
308
conductors max
12 AWG THHN
225
conductors max
10 AWG THHN
141
conductors max
Usable area at 40% fill: 2.99 in² · NEC Chapter 9, Tables 1, 4 and 5

About Liquidtight (LFMC) (Liquidtight Flexible Metal Conduit (LFMC))

Flexible metal conduit with a sunlight- and oil-resistant thermoplastic jacket. The usual choice for outdoor equipment whips: air conditioners, pumps, rooftop units. Trade size 3" is covered by NEC Article 350, and its internal dimensions come from NEC Chapter 9, Table 4.

3" Liquidtight (LFMC) — Internal Area & Fill Limits

Trade size3"
Total internal area (100%)7.475 in²
1 conductor (53%)3.962 in²
2 conductors (31%)2.317 in²
Over 2 conductors (40%)2.99 in²

3" Liquidtight (LFMC) — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.0097308
120.0133225
100.0211141
80.036681
60.050759
40.082436
30.097330
20.115826
10.156219
1/00.185516
2/00.222313
3/00.267911
4/00.32379
250 kcmil0.39707
300 kcmil0.46086
350 kcmil0.52425
400 kcmil0.58635
500 kcmil0.70734
600 kcmil0.86763
700 kcmil0.98873
750 kcmil1.04963
800 kcmil1.10852
900 kcmil1.23111
1000 kcmil1.34781
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

3" Liquidtight (LFMC) — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.0139215
120.0181165
100.0243123
80.043768
60.059050
40.081436
30.096231
20.114626
10.153419
1/00.182516
2/00.219013
3/00.264211
4/00.31979
250 kcmil0.39047
300 kcmil0.45366
350 kcmil0.51665
400 kcmil0.57825
500 kcmil0.69844
600 kcmil0.87093
700 kcmil0.99233
750 kcmil1.05323
800 kcmil1.11222
900 kcmil1.23511
1000 kcmil1.35191
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 3" Liquidtight (LFMC) with 12 AWG THHN: 7.475 × 0.40 ÷ 0.0133 = 224.81 → 225 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 3" Liquidtight (LFMC) that raises the usable area from 2.99 in² to 4.485 in².

Other Liquidtight (LFMC) Sizes

3" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 3-inch Liquidtight Flexible Metal Conduit conduit?

A 3-inch Liquidtight Flexible Metal Conduit conduit has 7.475 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 2.99 in². That works out to 225 #12 THHN, 308 #14 THHN, 141 #10 THHN, or 81 #8 THHN conductors.

How many 12 AWG THHN wires fit in 3-inch Liquidtight Flexible Metal Conduit?

225 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 3-inch Liquidtight Flexible Metal Conduit is 2.99 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.

Related