1-1/4" Liquidtight (LFMC) Conduit Fill Chart

14 AWG THHN
63
conductors max
12 AWG THHN
46
conductors max
10 AWG THHN
29
conductors max
Usable area at 40% fill: 0.611 in² · NEC Chapter 9, Tables 1, 4 and 5

About Liquidtight (LFMC) (Liquidtight Flexible Metal Conduit (LFMC))

Flexible metal conduit with a sunlight- and oil-resistant thermoplastic jacket. The usual choice for outdoor equipment whips: air conditioners, pumps, rooftop units. Trade size 1-1/4" is covered by NEC Article 350, and its internal dimensions come from NEC Chapter 9, Table 4.

1-1/4" Liquidtight (LFMC) — Internal Area & Fill Limits

Trade size1-1/4"
Total internal area (100%)1.528 in²
1 conductor (53%)0.81 in²
2 conductors (31%)0.474 in²
Over 2 conductors (40%)0.611 in²

1-1/4" Liquidtight (LFMC) — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.009763
120.013346
100.021129
80.036616
60.050712
40.08247
30.09736
20.11585
10.15624
1/00.18553
2/00.22232
3/00.26791
4/00.32371
250 kcmil0.39701
300 kcmil0.46081
350 kcmil0.52421
400 kcmil0.58631
500 kcmil0.70731
600 kcmil0.8676—
700 kcmil0.9887—
750 kcmil1.0496—
800 kcmil1.1085—
900 kcmil1.2311—
1000 kcmil1.3478—
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

1-1/4" Liquidtight (LFMC) — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.013944
120.018133
100.024325
80.043714
60.059010
40.08147
30.09626
20.11465
10.15344
1/00.18253
2/00.21902
3/00.26421
4/00.31971
250 kcmil0.39041
300 kcmil0.45361
350 kcmil0.51661
400 kcmil0.57821
500 kcmil0.69841
600 kcmil0.8709—
700 kcmil0.9923—
750 kcmil1.0532—
800 kcmil1.1122—
900 kcmil1.2351—
1000 kcmil1.3519—
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 1-1/4" Liquidtight (LFMC) with 12 AWG THHN: 1.528 × 0.40 ÷ 0.0133 = 45.95 → 46 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 1-1/4" Liquidtight (LFMC) that raises the usable area from 0.611 in² to 0.917 in².

Other Liquidtight (LFMC) Sizes

1-1/4" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 1-1/4-inch Liquidtight Flexible Metal Conduit conduit?

A 1-1/4-inch Liquidtight Flexible Metal Conduit conduit has 1.528 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 0.611 in². That works out to 46 #12 THHN, 63 #14 THHN, 29 #10 THHN, or 16 #8 THHN conductors.

How many 12 AWG THHN wires fit in 1-1/4-inch Liquidtight Flexible Metal Conduit?

46 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 1-1/4-inch Liquidtight Flexible Metal Conduit is 0.611 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.

Related

Conduit fill calculator → All conduit fill charts → Ampacity tables →