2" Liquidtight (LFMC) Conduit Fill Chart

14 AWG THHN
134
conductors max
12 AWG THHN
97
conductors max
10 AWG THHN
61
conductors max
Usable area at 40% fill: 1.298 in² · NEC Chapter 9, Tables 1, 4 and 5

About Liquidtight (LFMC) (Liquidtight Flexible Metal Conduit (LFMC))

Flexible metal conduit with a sunlight- and oil-resistant thermoplastic jacket. The usual choice for outdoor equipment whips: air conditioners, pumps, rooftop units. Trade size 2" is covered by NEC Article 350, and its internal dimensions come from NEC Chapter 9, Table 4.

2" Liquidtight (LFMC) — Internal Area & Fill Limits

Trade size2"
Total internal area (100%)3.246 in²
1 conductor (53%)1.72 in²
2 conductors (31%)1.006 in²
Over 2 conductors (40%)1.298 in²

2" Liquidtight (LFMC) — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.0097134
120.013397
100.021161
80.036635
60.050725
40.082415
30.097313
20.115811
10.15628
1/00.18557
2/00.22236
3/00.26795
4/00.32374
250 kcmil0.39703
300 kcmil0.46083
350 kcmil0.52421
400 kcmil0.58631
500 kcmil0.70731
600 kcmil0.86761
700 kcmil0.98871
750 kcmil1.04961
800 kcmil1.10851
900 kcmil1.23111
1000 kcmil1.34781
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

2" Liquidtight (LFMC) — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.013993
120.018171
100.024353
80.043729
60.059022
40.081416
30.096213
20.114611
10.15348
1/00.18257
2/00.21906
3/00.26425
4/00.31974
250 kcmil0.39043
300 kcmil0.45363
350 kcmil0.51661
400 kcmil0.57821
500 kcmil0.69841
600 kcmil0.87091
700 kcmil0.99231
750 kcmil1.05321
800 kcmil1.11221
900 kcmil1.23511
1000 kcmil1.35191
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 2" Liquidtight (LFMC) with 12 AWG THHN: 3.246 × 0.40 ÷ 0.0133 = 97.62 → 97 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 2" Liquidtight (LFMC) that raises the usable area from 1.298 in² to 1.948 in².

Other Liquidtight (LFMC) Sizes

2" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 2-inch Liquidtight Flexible Metal Conduit conduit?

A 2-inch Liquidtight Flexible Metal Conduit conduit has 3.246 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 1.298 in². That works out to 97 #12 THHN, 134 #14 THHN, 61 #10 THHN, or 35 #8 THHN conductors.

How many 12 AWG THHN wires fit in 2-inch Liquidtight Flexible Metal Conduit?

97 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 2-inch Liquidtight Flexible Metal Conduit is 1.298 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.