2" PVC Sch 40 Conduit Fill Chart

14 AWG THHN
135
conductors max
12 AWG THHN
98
conductors max
10 AWG THHN
62
conductors max
Usable area at 40% fill: 1.316 in² · NEC Chapter 9, Tables 1, 4 and 5

About PVC Conduit, Schedule 40

Rigid nonmetallic conduit, solvent-welded. The default for underground runs, wet locations, and corrosive environments. Schedule 80 has thicker walls and therefore less usable fill area. Trade size 2" is covered by NEC Article 352, and its internal dimensions come from NEC Chapter 9, Table 4.

2" PVC Sch 40 — Internal Area & Fill Limits

Trade size2"
Total internal area (100%)3.291 in²
1 conductor (53%)1.744 in²
2 conductors (31%)1.020 in²
Over 2 conductors (40%)1.316 in²

2" PVC Sch 40 — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.0097135
120.013398
100.021162
80.036635
60.050725
40.082415
30.097313
20.115811
10.15628
1/00.18557
2/00.22235
3/00.26794
4/00.32374
250 kcmil0.39703
300 kcmil0.46082
350 kcmil0.52421
400 kcmil0.58631
500 kcmil0.70731
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type, which is the condition NEC Annex C tables are built on. Mix sizes or insulations and you must add the individual areas by hand against the fill area above.

2" PVC Sch 40 — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.013994
120.018172
100.024354
80.043730
60.059022
40.081416
30.096213
20.114611
10.15348
1/00.18257
2/00.21906
3/00.26424
4/00.31974
250 kcmil0.39043
350 kcmil0.51531
500 kcmil0.69841
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. From 4 AWG up they are slightly smaller. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down — you cannot install a fraction of a wire.

Max conductors = floor( conduit area × fill % ÷ conductor area )

For 2" PVC Sch 40 with 12 AWG THHN: floor( 3.291 × 0.40 ÷ 0.0133 ) = 98 conductors

The three percentages in NEC Chapter 9, Table 1 are not arbitrary. A single conductor gets 53% because it can be pulled straight down the middle. Exactly two conductors get only 31% because two circles inside a circle waste the most space. Three or more conductors nest efficiently again, so the limit rises to 40%.

Fill is only half the job. Once you have more than three current-carrying conductors in the same raceway, NEC 310.15(C)(1) also derates their ampacity — 80% for 4–6 conductors, 70% for 7–9, 50% for 10–20. A conduit can be legally filled and still leave your conductors undersized for the load. See NEC Table 310.15 for the full derating factors.

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4 — and no ampacity derating applies to it. For 2" PVC Sch 40 that raises the usable area from 1.316 in² to 1.975 in².