1/2" PVC Sch 40 Conduit Fill Chart

14 AWG THHN
11
conductors max
12 AWG THHN
8
conductors max
10 AWG THHN
5
conductors max
Usable area at 40% fill: 0.114 in² · NEC Chapter 9, Tables 1, 4 and 5

About PVC Conduit, Schedule 40

Rigid nonmetallic conduit, solvent-welded. The default for underground runs, wet locations, and corrosive environments. Schedule 80 has thicker walls and therefore less usable fill area. Trade size 1/2" is covered by NEC Article 352, and its internal dimensions come from NEC Chapter 9, Table 4.

1/2" PVC Sch 40 — Internal Area & Fill Limits

Trade size1/2"
Total internal area (100%)0.285 in²
1 conductor (53%)0.151 in²
2 conductors (31%)0.088 in²
Over 2 conductors (40%)0.114 in²

1/2" PVC Sch 40 — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.009711
120.01338
100.02115
80.03663
60.05071
40.08241
30.09731
20.11581
10.1562
1/00.1855
2/00.2223
3/00.2679
4/00.3237
250 kcmil0.3970
300 kcmil0.4608
350 kcmil0.5242
400 kcmil0.5863
500 kcmil0.7073
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type, which is the condition NEC Annex C tables are built on. Mix sizes or insulations and you must add the individual areas by hand against the fill area above.

1/2" PVC Sch 40 — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.01398
120.01816
100.02434
80.04372
60.05901
40.08141
30.09621
20.11461
10.1534
1/00.1825
2/00.2190
3/00.2642
4/00.3197
250 kcmil0.3904
350 kcmil0.5153
500 kcmil0.6984
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. From 4 AWG up they are slightly smaller. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down — you cannot install a fraction of a wire.

Max conductors = floor( conduit area × fill % ÷ conductor area )

For 1/2" PVC Sch 40 with 12 AWG THHN: floor( 0.285 × 0.40 ÷ 0.0133 ) = 8 conductors

The three percentages in NEC Chapter 9, Table 1 are not arbitrary. A single conductor gets 53% because it can be pulled straight down the middle. Exactly two conductors get only 31% because two circles inside a circle waste the most space. Three or more conductors nest efficiently again, so the limit rises to 40%.

Fill is only half the job. Once you have more than three current-carrying conductors in the same raceway, NEC 310.15(C)(1) also derates their ampacity — 80% for 4–6 conductors, 70% for 7–9, 50% for 10–20. A conduit can be legally filled and still leave your conductors undersized for the load. See NEC Table 310.15 for the full derating factors.

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4 — and no ampacity derating applies to it. For 1/2" PVC Sch 40 that raises the usable area from 0.114 in² to 0.171 in².