WireSizing
Wire gauge reference & calculator

1" PVC Sch 40 Conduit Fill Chart

14 AWG THHN
34
conductors max
12 AWG THHN
25
conductors max
10 AWG THHN
15
conductors max
Usable area at 40% fill: 0.333 in² · NEC Chapter 9, Tables 1, 4 and 5

About PVC Conduit, Schedule 40

Rigid nonmetallic conduit, solvent-welded. The default for underground runs, wet locations, and corrosive environments. Schedule 80 has thicker walls and therefore less usable fill area. Trade size 1" is covered by NEC Article 352, and its internal dimensions come from NEC Chapter 9, Table 4.

1" PVC Sch 40 — Internal Area & Fill Limits

Trade size1"
Total internal area (100%)0.832 in²
1 conductor (53%)0.441 in²
2 conductors (31%)0.258 in²
Over 2 conductors (40%)0.333 in²

1" PVC Sch 40 — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.009734
120.013325
100.021115
80.03669
60.05076
40.08244
30.09733
20.11583
10.15621
1/00.18551
2/00.22231
3/00.26791
4/00.32371
250 kcmil0.39701
300 kcmil0.4608—
350 kcmil0.5242—
400 kcmil0.5863—
500 kcmil0.7073—
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type, which is the condition NEC Annex C tables are built on. Mix sizes or insulations and you must add the individual areas by hand against the fill area above.

1" PVC Sch 40 — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.013924
120.018118
100.024313
80.04377
60.05905
40.08144
30.09623
20.11463
10.15341
1/00.18251
2/00.21901
3/00.26421
4/00.31971
250 kcmil0.39041
350 kcmil0.5153—
500 kcmil0.6984—
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. From 4 AWG up they are slightly smaller. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 1" PVC Sch 40 with 12 AWG THHN: 0.832 × 0.40 ÷ 0.0133 = 25.02 → 25 conductors

The three percentages in NEC Chapter 9, Table 1 are not arbitrary. A single conductor gets 53% because it can be pulled straight down the middle. Exactly two conductors get only 31% because two circles inside a circle waste the most space. Three or more conductors nest efficiently again, so the limit rises to 40%.

Fill is only half the job. Once you have more than three current-carrying conductors in the same raceway, NEC 310.15(C)(1) also derates their ampacity — 80% for 4–6 conductors, 70% for 7–9, 50% for 10–20. A conduit can be legally filled and still leave your conductors undersized for the load. See NEC Table 310.15 for the full derating factors.

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4 — and no ampacity derating applies to it. For 1" PVC Sch 40 that raises the usable area from 0.333 in² to 0.499 in².

Other PVC Sch 40 Sizes

1" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 1-inch PVC Sch 40 conduit?

A 1-inch PVC Sch 40 conduit has 0.832 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 0.333 in². That works out to 25 #12 THHN, 34 #14 THHN, 15 #10 THHN, or 9 #8 THHN conductors.

How many 12 AWG THHN wires fit in 1-inch PVC Sch 40?

25 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 1-inch PVC Sch 40 is 0.333 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.

Does the equipment grounding conductor count toward conduit fill?

Yes. Every conductor in the raceway counts toward the cross-sectional fill calculation, including equipment grounding conductors and neutrals. Grounding conductors do not count as current-carrying conductors for the separate NEC 310.15(C)(1) derating calculation, but they still occupy space.

Related

Conduit fill calculator → All conduit fill charts → THHN / THWN wire specifications → NEC Table 310.15 derating factors → Ampacity tables →