Maximum number of THHN/THWN-2 conductors in PVC Conduit, Schedule 40, trade sizes 1/2 inch through 4 inch. Internal areas from NEC Chapter 9, Table 4; fill limits from Table 1 (53% for one conductor, 31% for two, 40% for three or more). NEC Article 352.

Trade size 40% area (in²) 14121086421/02/04/0
1/2"0.11411853111
3/4"0.20320159541111
1"0.3333425159642111
1-1/4"0.581594327151175321
1-1/2"0.794815937211596431
2"1.316135986235251511754
2-1/2"1.87819314189513722161085
3"2.9072992181377957352515138
3-1/2"3.895401292184106764733201712
4"5.022517377238137996043272215

Column headings are AWG conductor sizes, all THHN/THWN-2. A dash means the conductor does not fit even as a single conductor at the 53% limit.

About PVC Conduit, Schedule 40

Rigid nonmetallic conduit, solvent-welded. The default for underground runs, wet locations, and corrosive environments. Schedule 80 has thicker walls and therefore less usable fill area.

PVC Sch 40 Fill by Trade Size

1/2" PVC Sch 40
8 × 12 AWG THHN · 0.114 in² usable
3/4" PVC Sch 40
15 × 12 AWG THHN · 0.203 in² usable
1" PVC Sch 40
25 × 12 AWG THHN · 0.333 in² usable
1-1/4" PVC Sch 40
43 × 12 AWG THHN · 0.581 in² usable
1-1/2" PVC Sch 40
59 × 12 AWG THHN · 0.794 in² usable
2" PVC Sch 40
98 × 12 AWG THHN · 1.316 in² usable
2-1/2" PVC Sch 40
141 × 12 AWG THHN · 1.878 in² usable
3" PVC Sch 40
218 × 12 AWG THHN · 2.907 in² usable
3-1/2" PVC Sch 40
292 × 12 AWG THHN · 3.895 in² usable
4" PVC Sch 40
377 × 12 AWG THHN · 5.022 in² usable