4" Liquidtight (LFMC) Conduit Fill Chart

14 AWG THHN
523
conductors max
12 AWG THHN
381
conductors max
10 AWG THHN
240
conductors max
Usable area at 40% fill: 5.077 in² · NEC Chapter 9, Tables 1, 4 and 5

About Liquidtight (LFMC) (Liquidtight Flexible Metal Conduit (LFMC))

Flexible metal conduit with a sunlight- and oil-resistant thermoplastic jacket. The usual choice for outdoor equipment whips: air conditioners, pumps, rooftop units. Trade size 4" is covered by NEC Article 350, and its internal dimensions come from NEC Chapter 9, Table 4.

4" Liquidtight (LFMC) — Internal Area & Fill Limits

Trade size4"
Total internal area (100%)12.692 in²
1 conductor (53%)6.727 in²
2 conductors (31%)3.935 in²
Over 2 conductors (40%)5.077 in²

4" Liquidtight (LFMC) — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.0097523
120.0133381
100.0211240
80.0366138
60.0507100
40.082461
30.097352
20.115844
10.156232
1/00.185527
2/00.222323
3/00.267919
4/00.323715
250 kcmil0.397012
300 kcmil0.460811
350 kcmil0.52429
400 kcmil0.58638
500 kcmil0.70737
600 kcmil0.86766
700 kcmil0.98875
750 kcmil1.04965
800 kcmil1.10854
900 kcmil1.23114
1000 kcmil1.34783
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

4" Liquidtight (LFMC) — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.0139365
120.0181280
100.0243209
80.0437116
60.059086
40.081462
30.096252
20.114644
10.153433
1/00.182528
2/00.219023
3/00.264219
4/00.319716
250 kcmil0.390413
300 kcmil0.453611
350 kcmil0.516610
400 kcmil0.57828
500 kcmil0.69847
600 kcmil0.87096
700 kcmil0.99235
750 kcmil1.05325
800 kcmil1.11224
900 kcmil1.23514
1000 kcmil1.35193
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 4" Liquidtight (LFMC) with 12 AWG THHN: 12.692 × 0.40 ÷ 0.0133 = 381.71 → 381 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 4" Liquidtight (LFMC) that raises the usable area from 5.077 in² to 7.615 in².

Other Liquidtight (LFMC) Sizes

4" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 4-inch Liquidtight Flexible Metal Conduit conduit?

A 4-inch Liquidtight Flexible Metal Conduit conduit has 12.692 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 5.077 in². That works out to 381 #12 THHN, 523 #14 THHN, 240 #10 THHN, or 138 #8 THHN conductors.

How many 12 AWG THHN wires fit in 4-inch Liquidtight Flexible Metal Conduit?

381 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 4-inch Liquidtight Flexible Metal Conduit is 5.077 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.