14 AWG THHN
562
conductors max
12 AWG THHN
409
conductors max
10 AWG THHN
258
conductors max
Usable area at 40% fill: 5.452 in² · NEC Chapter 9, Tables 1, 4 and 5

About Intermediate Metal Conduit (IMC)

Threaded steel conduit with a thinner wall than RMC, so it is lighter and has slightly more internal area. Permitted anywhere RMC is permitted. Trade size 4" is covered by NEC Article 342, and its internal dimensions come from NEC Chapter 9, Table 4.

4" IMC — Internal Area & Fill Limits

Trade size4"
Total internal area (100%)13.631 in²
1 conductor (53%)7.224 in²
2 conductors (31%)4.226 in²
Over 2 conductors (40%)5.452 in²

4" IMC — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.0097562
120.0133409
100.0211258
80.0366148
60.0507107
40.082466
30.097356
20.115847
10.156234
1/00.185529
2/00.222324
3/00.267920
4/00.323716
250 kcmil0.397013
300 kcmil0.460811
350 kcmil0.524210
400 kcmil0.58639
500 kcmil0.70737
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type, which is the condition NEC Annex C tables are built on. Mix sizes or insulations and you must add the individual areas by hand against the fill area above.

4" IMC — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.0139392
120.0181301
100.0243224
80.0437124
60.059092
40.081466
30.096256
20.114647
10.153435
1/00.182529
2/00.219024
3/00.264220
4/00.319717
250 kcmil0.390413
350 kcmil0.515310
500 kcmil0.69847
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. From 4 AWG up they are slightly smaller. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down — you cannot install a fraction of a wire.

Max conductors = floor( conduit area × fill % ÷ conductor area )

For 4" IMC with 12 AWG THHN: floor( 13.631 × 0.40 ÷ 0.0133 ) = 409 conductors

The three percentages in NEC Chapter 9, Table 1 are not arbitrary. A single conductor gets 53% because it can be pulled straight down the middle. Exactly two conductors get only 31% because two circles inside a circle waste the most space. Three or more conductors nest efficiently again, so the limit rises to 40%.

Fill is only half the job. Once you have more than three current-carrying conductors in the same raceway, NEC 310.15(C)(1) also derates their ampacity — 80% for 4–6 conductors, 70% for 7–9, 50% for 10–20. A conduit can be legally filled and still leave your conductors undersized for the load. See NEC Table 310.15 for the full derating factors.

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4 — and no ampacity derating applies to it. For 4" IMC that raises the usable area from 5.452 in² to 8.179 in².