2-1/2" Liquidtight (LFMC) Conduit Fill Chart

14 AWG THHN
201
conductors max
12 AWG THHN
146
conductors max
10 AWG THHN
92
conductors max
Usable area at 40% fill: 1.952 in² · NEC Chapter 9, Tables 1, 4 and 5

About Liquidtight (LFMC) (Liquidtight Flexible Metal Conduit (LFMC))

Flexible metal conduit with a sunlight- and oil-resistant thermoplastic jacket. The usual choice for outdoor equipment whips: air conditioners, pumps, rooftop units. Trade size 2-1/2" is covered by NEC Article 350, and its internal dimensions come from NEC Chapter 9, Table 4.

2-1/2" Liquidtight (LFMC) — Internal Area & Fill Limits

Trade size2-1/2"
Total internal area (100%)4.881 in²
1 conductor (53%)2.587 in²
2 conductors (31%)1.513 in²
Over 2 conductors (40%)1.952 in²

2-1/2" Liquidtight (LFMC) — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.0097201
120.0133146
100.021192
80.036653
60.050738
40.082423
30.097320
20.115817
10.156212
1/00.185510
2/00.22238
3/00.26797
4/00.32376
250 kcmil0.39705
300 kcmil0.46084
350 kcmil0.52423
400 kcmil0.58633
500 kcmil0.70732
600 kcmil0.86761
700 kcmil0.98871
750 kcmil1.04961
800 kcmil1.10851
900 kcmil1.23111
1000 kcmil1.34781
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

2-1/2" Liquidtight (LFMC) — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.0139140
120.0181108
100.024380
80.043744
60.059033
40.081424
30.096220
20.114617
10.153412
1/00.182510
2/00.21909
3/00.26427
4/00.31976
250 kcmil0.39045
300 kcmil0.45364
350 kcmil0.51663
400 kcmil0.57823
500 kcmil0.69842
600 kcmil0.87091
700 kcmil0.99231
750 kcmil1.05321
800 kcmil1.11221
900 kcmil1.23511
1000 kcmil1.35191
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 2-1/2" Liquidtight (LFMC) with 12 AWG THHN: 4.881 × 0.40 ÷ 0.0133 = 146.80 → 146 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 2-1/2" Liquidtight (LFMC) that raises the usable area from 1.952 in² to 2.929 in².

Other Liquidtight (LFMC) Sizes

2-1/2" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 2-1/2-inch Liquidtight Flexible Metal Conduit conduit?

A 2-1/2-inch Liquidtight Flexible Metal Conduit conduit has 4.881 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 1.952 in². That works out to 146 #12 THHN, 201 #14 THHN, 92 #10 THHN, or 53 #8 THHN conductors.

How many 12 AWG THHN wires fit in 2-1/2-inch Liquidtight Flexible Metal Conduit?

146 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 2-1/2-inch Liquidtight Flexible Metal Conduit is 1.952 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.