WireSizing
Wire gauge reference & calculator

Liquidtight (LFMC) Conduit Fill Chart

Maximum number of THHN/THWN-2 conductors in Liquidtight (LFMC) (Liquidtight Flexible Metal Conduit (LFMC)), trade sizes 3/8 inch through 4 inch. Internal areas from NEC Chapter 9, Table 4; fill limits from Table 1 (53% for one conductor, 31% for two, 40% for three or more). NEC Article 350.

Trade size 40% area (in²) 14121086421/02/04/0
3/8"0.077853111————
1/2"0.12613963111———
3/4"0.216221610642111—
1"0.3493626169743111
1-1/4"0.611634629161275321
1-1/2"0.792815937211597431
2"1.298134976135251511764
2-1/2"1.95220114692533823171086
3"2.993082251418159362616139
3-1/2"3.892401292184106764733211712
4"5.0775233812401381006144272315

Column headings are AWG conductor sizes, all THHN/THWN-2. A dash means the conductor does not fit even as a single conductor at the 53% limit.

About Liquidtight (LFMC) (Liquidtight Flexible Metal Conduit (LFMC))

Flexible metal conduit with a sunlight- and oil-resistant thermoplastic jacket. The usual choice for outdoor equipment whips: air conditioners, pumps, rooftop units.

Liquidtight (LFMC) Fill by Trade Size

3/8" Liquidtight (LFMC)
5 × 12 AWG THHN · 0.077 in² usable
1/2" Liquidtight (LFMC)
9 × 12 AWG THHN · 0.126 in² usable
3/4" Liquidtight (LFMC)
16 × 12 AWG THHN · 0.216 in² usable
1" Liquidtight (LFMC)
26 × 12 AWG THHN · 0.349 in² usable
1-1/4" Liquidtight (LFMC)
46 × 12 AWG THHN · 0.611 in² usable
1-1/2" Liquidtight (LFMC)
59 × 12 AWG THHN · 0.792 in² usable
2" Liquidtight (LFMC)
97 × 12 AWG THHN · 1.298 in² usable
2-1/2" Liquidtight (LFMC)
146 × 12 AWG THHN · 1.952 in² usable
3" Liquidtight (LFMC)
225 × 12 AWG THHN · 2.99 in² usable
3-1/2" Liquidtight (LFMC)
292 × 12 AWG THHN · 3.892 in² usable
4" Liquidtight (LFMC)
381 × 12 AWG THHN · 5.077 in² usable

Other Conduit Types

EMT Fill Chart
NEC Article 358
PVC Schedule 40 Fill Chart
NEC Article 352
PVC Schedule 80 Fill Chart
NEC Article 352
Rigid Metal (RMC) Fill Chart
NEC Article 344
IMC Fill Chart
NEC Article 342
Flexible Metal (FMC) Fill Chart
NEC Article 348
ENT Fill Chart
NEC Article 362

Related