WireSizing
Wire gauge reference & calculator

ENT Conduit Fill Chart

Maximum number of THHN/THWN-2 conductors in ENT (Electrical Nonmetallic Tubing), trade sizes 1/2 inch through 2 inch. Internal areas from NEC Chapter 9, Table 4; fill limits from Table 1 (53% for one conductor, 31% for two, 40% for three or more). NEC Article 362.

Trade size 40% area (in²) 14121086421/02/04/0
1/2"0.11411853111———
3/4"0.20321159541111—
1"0.3333425159643111
1-1/4"0.581604327161175321
1-1/2"0.794825937211597431
2"1.316135996236261611764

Column headings are AWG conductor sizes, all THHN/THWN-2. A dash means the conductor does not fit even as a single conductor at the 53% limit.

About ENT (Electrical Nonmetallic Tubing)

Corrugated pliable plastic tubing (“smurf tube”), bent by hand and used inside walls, above suspended ceilings and encased in concrete slabs. Current tables give it the same internal dimensions as Schedule 40 PVC.

ENT Fill by Trade Size

1/2" ENT
8 × 12 AWG THHN · 0.114 in² usable
3/4" ENT
15 × 12 AWG THHN · 0.203 in² usable
1" ENT
25 × 12 AWG THHN · 0.333 in² usable
1-1/4" ENT
43 × 12 AWG THHN · 0.581 in² usable
1-1/2" ENT
59 × 12 AWG THHN · 0.794 in² usable
2" ENT
99 × 12 AWG THHN · 1.316 in² usable

Other Conduit Types

EMT Fill Chart
NEC Article 358
PVC Schedule 40 Fill Chart
NEC Article 352
PVC Schedule 80 Fill Chart
NEC Article 352
Rigid Metal (RMC) Fill Chart
NEC Article 344
IMC Fill Chart
NEC Article 342
Flexible Metal (FMC) Fill Chart
NEC Article 348
Liquidtight (LFMC) Fill Chart
NEC Article 350

Related