Maximum number of THHN/THWN-2 conductors in ENT (Electrical Nonmetallic Tubing), trade sizes 1/2 inch through 2 inch. Internal areas from NEC Chapter 9, Table 4; fill limits from Table 1 (53% for one conductor, 31% for two, 40% for three or more). NEC Article 362.
| Trade size | 40% area (in²) | 14 | 12 | 10 | 8 | 6 | 4 | 2 | 1/0 | 2/0 | 4/0 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1/2" | 0.114 | 11 | 8 | 5 | 3 | 1 | 1 | 1 | — | — | — |
| 3/4" | 0.203 | 21 | 15 | 9 | 5 | 4 | 1 | 1 | 1 | 1 | — |
| 1" | 0.333 | 34 | 25 | 15 | 9 | 6 | 4 | 3 | 1 | 1 | 1 |
| 1-1/4" | 0.581 | 60 | 43 | 27 | 16 | 11 | 7 | 5 | 3 | 2 | 1 |
| 1-1/2" | 0.794 | 82 | 59 | 37 | 21 | 15 | 9 | 7 | 4 | 3 | 1 |
| 2" | 1.316 | 135 | 99 | 62 | 36 | 26 | 16 | 11 | 7 | 6 | 4 |
Column headings are AWG conductor sizes, all THHN/THWN-2. A dash means the conductor does not fit even as a single conductor at the 53% limit.
Corrugated pliable plastic tubing (“smurf tube”), bent by hand and used inside walls, above suspended ceilings and encased in concrete slabs. Current tables give it the same internal dimensions as Schedule 40 PVC.