1" ENT Conduit Fill Chart

14 AWG THHN
34
conductors max
12 AWG THHN
25
conductors max
10 AWG THHN
15
conductors max
Usable area at 40% fill: 0.333 in² · NEC Chapter 9, Tables 1, 4 and 5

About ENT (Electrical Nonmetallic Tubing)

Corrugated pliable plastic tubing (“smurf tube”), bent by hand and used inside walls, above suspended ceilings and encased in concrete slabs. Current tables give it the same internal dimensions as Schedule 40 PVC. Trade size 1" is covered by NEC Article 362, and its internal dimensions come from NEC Chapter 9, Table 4.

1" ENT — Internal Area & Fill Limits

Trade size1"
Total internal area (100%)0.832 in²
1 conductor (53%)0.441 in²
2 conductors (31%)0.258 in²
Over 2 conductors (40%)0.333 in²

1" ENT — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.009734
120.013325
100.021115
80.03669
60.05076
40.08244
30.09733
20.11583
10.15621
1/00.18551
2/00.22231
3/00.26791
4/00.32371
250 kcmil0.39701
300 kcmil0.4608—
350 kcmil0.5242—
400 kcmil0.5863—
500 kcmil0.7073—
600 kcmil0.8676—
700 kcmil0.9887—
750 kcmil1.0496—
800 kcmil1.1085—
900 kcmil1.2311—
1000 kcmil1.3478—
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

1" ENT — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.013924
120.018118
100.024313
80.04377
60.05905
40.08144
30.09623
20.11463
10.15341
1/00.18251
2/00.21901
3/00.26421
4/00.31971
250 kcmil0.39041
300 kcmil0.4536—
350 kcmil0.5166—
400 kcmil0.5782—
500 kcmil0.6984—
600 kcmil0.8709—
700 kcmil0.9923—
750 kcmil1.0532—
800 kcmil1.1122—
900 kcmil1.2351—
1000 kcmil1.3519—
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 1" ENT with 12 AWG THHN: 0.832 × 0.40 ÷ 0.0133 = 25.02 → 25 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 1" ENT that raises the usable area from 0.333 in² to 0.499 in².

Other ENT Sizes

1" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 1-inch ENT conduit?

A 1-inch ENT conduit has 0.832 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 0.333 in². That works out to 25 #12 THHN, 34 #14 THHN, 15 #10 THHN, or 9 #8 THHN conductors.

How many 12 AWG THHN wires fit in 1-inch ENT?

25 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 1-inch ENT is 0.333 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.

Related

Conduit fill calculator → All conduit fill charts → Ampacity tables →