Corrugated pliable plastic tubing (“smurf tube”), bent by hand and used inside walls, above suspended ceilings and encased in concrete slabs. Current tables give it the same internal dimensions as Schedule 40 PVC. Trade size 1-1/4" is covered by NEC Article 362, and its internal dimensions come from NEC Chapter 9, Table 4.
| Trade size | 1-1/4" |
| Total internal area (100%) | 1.453 in² |
| 1 conductor (53%) | 0.77 in² |
| 2 conductors (31%) | 0.45 in² |
| Over 2 conductors (40%) | 0.581 in² |
| Wire size | Area (in²) | Max conductors |
|---|---|---|
| 14 | 0.0097 | 60 |
| 12 | 0.0133 | 43 |
| 10 | 0.0211 | 27 |
| 8 | 0.0366 | 16 |
| 6 | 0.0507 | 11 |
| 4 | 0.0824 | 7 |
| 3 | 0.0973 | 6 |
| 2 | 0.1158 | 5 |
| 1 | 0.1562 | 3 |
| 1/0 | 0.1855 | 3 |
| 2/0 | 0.2223 | 2 |
| 3/0 | 0.2679 | 1 |
| 4/0 | 0.3237 | 1 |
| 250 kcmil | 0.3970 | 1 |
| 300 kcmil | 0.4608 | 1 |
| 350 kcmil | 0.5242 | 1 |
| 400 kcmil | 0.5863 | 1 |
| 500 kcmil | 0.7073 | 1 |
| 600 kcmil | 0.8676 | — |
| 700 kcmil | 0.9887 | — |
| 750 kcmil | 1.0496 | — |
| 800 kcmil | 1.1085 | — |
| 900 kcmil | 1.2311 | — |
| 1000 kcmil | 1.3478 | — |
| Wire size | Area (in²) | Max conductors |
|---|---|---|
| 14 | 0.0139 | 42 |
| 12 | 0.0181 | 32 |
| 10 | 0.0243 | 24 |
| 8 | 0.0437 | 13 |
| 6 | 0.0590 | 10 |
| 4 | 0.0814 | 7 |
| 3 | 0.0962 | 6 |
| 2 | 0.1146 | 5 |
| 1 | 0.1534 | 3 |
| 1/0 | 0.1825 | 3 |
| 2/0 | 0.2190 | 2 |
| 3/0 | 0.2642 | 1 |
| 4/0 | 0.3197 | 1 |
| 250 kcmil | 0.3904 | 1 |
| 300 kcmil | 0.4536 | 1 |
| 350 kcmil | 0.5166 | 1 |
| 400 kcmil | 0.5782 | 1 |
| 500 kcmil | 0.6984 | 1 |
| 600 kcmil | 0.8709 | — |
| 700 kcmil | 0.9923 | — |
| 750 kcmil | 1.0532 | — |
| 800 kcmil | 1.1122 | — |
| 900 kcmil | 1.2351 | — |
| 1000 kcmil | 1.3519 | — |
Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.
Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)
For 1-1/4" ENT with 12 AWG THHN: 1.453 × 0.40 ÷ 0.0133 = 43.70 → 43 conductors
Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 1-1/4" ENT that raises the usable area from 0.581 in² to 0.872 in².
A 1-1/4-inch ENT conduit has 1.453 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 0.581 in². That works out to 43 #12 THHN, 60 #14 THHN, 27 #10 THHN, or 16 #8 THHN conductors.
43 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 1-1/4-inch ENT is 0.581 in².
NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.