1-1/2" ENT Conduit Fill Chart

14 AWG THHN
82
conductors max
12 AWG THHN
59
conductors max
10 AWG THHN
37
conductors max
Usable area at 40% fill: 0.794 in² · NEC Chapter 9, Tables 1, 4 and 5

About ENT (Electrical Nonmetallic Tubing)

Corrugated pliable plastic tubing (“smurf tube”), bent by hand and used inside walls, above suspended ceilings and encased in concrete slabs. Current tables give it the same internal dimensions as Schedule 40 PVC. Trade size 1-1/2" is covered by NEC Article 362, and its internal dimensions come from NEC Chapter 9, Table 4.

1-1/2" ENT — Internal Area & Fill Limits

Trade size1-1/2"
Total internal area (100%)1.986 in²
1 conductor (53%)1.053 in²
2 conductors (31%)0.616 in²
Over 2 conductors (40%)0.794 in²

1-1/2" ENT — Max THHN / THWN-2 Conductors

Wire size Area (in²) Max conductors
140.009782
120.013359
100.021137
80.036621
60.050715
40.08249
30.09738
20.11587
10.15625
1/00.18554
2/00.22233
3/00.26793
4/00.32371
250 kcmil0.39701
300 kcmil0.46081
350 kcmil0.52421
400 kcmil0.58631
500 kcmil0.70731
600 kcmil0.86761
700 kcmil0.98871
750 kcmil1.04961
800 kcmil1.1085—
900 kcmil1.2311—
1000 kcmil1.3478—
Conductor areas from NEC Chapter 9, Table 5 (THHN, THWN, THWN-2). Counts assume all conductors are the same size and insulation type.

1-1/2" ENT — Max XHHW / XHHW-2 Conductors

Wire size Area (in²) Max conductors
140.013957
120.018144
100.024332
80.043718
60.059013
40.08149
30.09628
20.11467
10.15345
1/00.18254
2/00.21903
3/00.26423
4/00.31971
250 kcmil0.39041
300 kcmil0.45361
350 kcmil0.51661
400 kcmil0.57821
500 kcmil0.69841
600 kcmil0.87091
700 kcmil0.99231
750 kcmil1.0532—
800 kcmil1.1122—
900 kcmil1.2351—
1000 kcmil1.3519—
XHHW and XHHW-2 have no nylon jacket, so below 4 AWG they are physically larger than THHN and fewer fit. Areas from NEC Chapter 9, Table 5.

How the 40% conduit fill rule works

Conduit fill is a pure area calculation. Take the internal area of the raceway from NEC Chapter 9, Table 4, multiply by the allowable percentage from Table 1, then divide by the area of one conductor from Table 5. Round down, except that NEC Chapter 9, Note 7 lets you round up to the next whole number when the result has a decimal of 0.8 or more and all conductors are the same size.

Max conductors = conduit area × fill % ÷ conductor area (Note 7 rounding)

For 1-1/2" ENT with 12 AWG THHN: 1.986 × 0.40 ÷ 0.0133 = 59.73 → 59 conductors

Nipples are the exception: a conduit or tubing length not exceeding 24 inches between boxes or enclosures may be filled to 60% per NEC Chapter 9, Table 1, Note 4. For 1-1/2" ENT that raises the usable area from 0.794 in² to 1.192 in².

Other ENT Sizes

1-1/2" in Other Conduit Types

Frequently Asked Questions

How many wires fit in 1-1/2-inch ENT conduit?

A 1-1/2-inch ENT conduit has 1.986 square inches of internal area. With more than two conductors the NEC limits fill to 40%, or 0.794 in². That works out to 59 #12 THHN, 82 #14 THHN, 37 #10 THHN, or 21 #8 THHN conductors.

How many 12 AWG THHN wires fit in 1-1/2-inch ENT?

59 conductors. Each 12 AWG THHN wire is 0.0133 in² per NEC Chapter 9, Table 5, and the 40% fill area of 1-1/2-inch ENT is 0.794 in².

What is the maximum fill percentage for conduit?

NEC Chapter 9, Table 1 sets three limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more. The lower two-conductor figure exists because two round conductors pack poorly inside a round raceway.